CSLB C-20 HVAC Contractor flashcards
197 free flashcards. Tap a card to flip it.
High-Pressure Switch
Flip cardA safety control that opens the compressor circuit when discharge pressure exceeds a factory-set limit, protecting the compressor and system from overpressure damage.
- Wired in series with the compressor contactor coil
- Trips on high discharge pressure (e.g., dirty condenser, overcharge, fan failure)
- Manual-reset types require investigation before resetting
Memory trick: High pressure hits the brakes before things blow.
Manual J Occupant Load
Flip cardManual J estimates internal sensible heat gain from occupants using a default occupancy count of bedrooms plus one, multiplied by a standard per-person Btu/hr allowance.
- Default occupancy = bedrooms + 1
- Standard sensible gain ≈ 230 Btu/hr per person
- Occupant gain is added to internal gains, separate from appliance loads
Memory trick: Bedrooms plus one, times 230, sums the sun (people) load.
Suction Line Accumulator
Flip cardA component that traps liquid refrigerant and oil returning from the evaporator, preventing compressor flooding and slugging, common on heat pumps.
- Common on heat pumps due to defrost cycle liquid floodback
- Meters liquid back slowly via bleed hole
- Protects against compressor mechanical damage
Memory trick: Accumulator holds the liquid hostage until it's safe.
Altitude Derating of Gas Furnaces
Flip cardCombustion equipment input capacity must be reduced above 2,000 ft elevation because thinner air reduces oxygen available for combustion, typically at a rate of about 4% per 1,000 ft above 2,000 ft.
- Threshold begins at 2,000 ft elevation
- Standard derate ~4% per 1,000 ft above threshold
- Affects heating input capacity and combustion efficiency
Memory trick: Above two grand, cut four percent per thousand you stand.
Low Charge Diagnostic Pattern
Flip cardA system low on refrigerant charge typically shows low suction pressure, high superheat, low subcooling, and reduced capacity simultaneously.
- Low suction pressure due to reduced refrigerant mass flow
- High superheat from early vapor formation in evaporator
- Low subcooling from insufficient liquid refrigerant in condenser
- Common root cause is a refrigerant leak
Memory trick: Low charge = low everything except superheat, which climbs high.
Heat Pump O/B Terminals
Flip cardO and B terminals control the reversing valve solenoid; O-type valves energize in cooling, B-type valves energize in heating, depending on manufacturer.
- O = Energized in Cooling (common convention)
- B = Energized in Heating (opposite convention)
- Wiring mismatch causes system to run in wrong mode
Memory trick: 'O' is for 'On in cOOling'; mismatched wiring flips the season.
MERV vs Pressure Drop
Flip cardHigher-MERV filters have finer media that increase resistance to airflow, raising static pressure if the system was not designed for it.
- Same-size filter, higher MERV = more restriction.
- Can cause reduced CFM, coil freezing, or blower strain.
- Media surface area and depth can offset restriction in properly designed filters.
Memory trick: Finer filter, harder to breathe through.
Low-Voltage Wire Sizing
Flip cardThermostat/control wire gauge must increase with run distance to limit voltage drop, since thinner wire has higher resistance per foot.
- 18 AWG: up to ~100 ft
- 16 AWG: ~100–200 ft
- 14 AWG: ~200–300 ft
- Excessive voltage drop causes erratic relay/thermostat operation
Memory trick: Longer run, thicker wire—resistance adds up like tolls on a highway.
Vent Connector Clearance
Flip cardSingle-wall metal vent connectors require 6 inches of clearance to combustible materials, while listed Type B double-wall connectors only require 1 inch due to their insulating air space.
- Single-wall: 6 in. clearance minimum
- Type B double-wall: 1 in. clearance (when listed)
- Clearance reduction possible only with listed protective shielding
Memory trick: Single-wall needs six; Type B only needs one.
SEER2 Test Procedure Change
Flip cardSEER2 uses the updated DOE M1 test procedure with higher, more realistic external static pressure than the older SEER test, resulting in lower numerical ratings for similar equipment.
- SEER2 test uses about 0.5 in. w.c. static pressure vs. 0.1 in. w.c. for SEER
- Reflects real-world duct restriction more accurately
- SEER2 and SEER numbers are not directly comparable
Memory trick: SEER2 turns up the duct resistance dial, so the number takes a dial-down.
Trunk Duct Reduction
Flip cardIn Manual D design, trunk duct size decreases progressively downstream as each branch takeoff removes airflow, allowing smaller duct sizes further from the plenum.
- Trunk CFM = total minus all upstream branch takeoffs
- Reducing trunk size downstream saves material and maintains velocity
- Oversized downstream trunk can cause excessive noise/turbulence
Memory trick: Every branch takes a bite out of the trunk's CFM.
AHRI Standard 700 (Reclaim Purity)
Flip cardThe industry standard specifying chemical purity requirements that recovered refrigerant must meet before being reclaimed and resold for reuse in another owner's system.
- Reclaimed refrigerant must be processed by an EPA-certified reclaimer
- AHRI 700 sets limits on moisture, acidity, high-boiling residue, and non-condensables
- Recycled refrigerant (not reclaimed) can only be reused by the same owner without meeting AHRI 700
Memory trick: To sell it clean, hit the AHRI 700 scene.
Compressor Flooding/Slugging
Flip cardA condition where liquid refrigerant returns to the compressor due to insufficient superheat, risking mechanical damage from incompressible liquid entering the compression chamber.
- Zero or near-zero superheat indicates floodback risk
- Slugging can break valves, reeds, or scroll sets instantly
- Suction line accumulators help protect against floodback
Memory trick: Zero superheat, liquid's a threat — slug the compressor, cause regret.
Lockout/Tagout Verification
Flip cardAfter isolating and locking an energy source, Cal/OSHA requires the worker to verify de-energization by testing the circuit with a meter or attempting to operate the equipment.
- Steps: identify, notify, isolate, lock/tag, verify (try-out/test)
- A meter reading of zero volts confirms de-energization
- Skipping verification is a leading cause of electrical injuries
Memory trick: Lock it, tag it, then TEST it.
Combustion Air Sizing (Two Openings, Outdoor Air)
Flip cardWhen combustion air comes from outdoors via two permanent openings, each opening requires 1 sq in of free area per 4,000 BTU/hr of appliance input.
- Openings placed within 12 in. of top and bottom of enclosure.
- Indoor air two-opening method instead uses 1 sq in per 1,000 BTU/hr.
- Confined spaces need adequate combustion, ventilation, and dilution air.
Memory trick: Outdoor air: four-thousand per inch.
EPA Venting Prohibition
Flip cardFederal law under Section 608 of the Clean Air Act prohibits knowingly venting refrigerants to the atmosphere during service, maintenance, or disposal.
- Applies to all refrigerants, including substitutes like R-410A
- Recovery equipment must be EPA-certified
- Violations carry civil penalties
Memory trick: Never let it fly — recover before you pry.
Ton of Cooling Conversion
Flip cardOne ton of air conditioning capacity equals 12,000 Btu/hr, used to convert calculated loads into standard equipment sizes.
- 1 ton = 12,000 Btu/hr
- Manual S matches equipment tonnage to Manual J load
- Oversizing by more than 15% can cause poor humidity control
Memory trick: Twelve thousand Btu makes one ton — remember the golden conversion.
R-410A vs R-22 Pressure Ratings
Flip cardR-410A operates at significantly higher system pressures than R-22, requiring gauges, hoses, and recovery equipment specifically rated for its higher pressure range.
- R-410A pressures run roughly 50-60% higher than R-22 at the same temperature
- Using R-22-rated equipment on R-410A systems risks equipment failure
- Always verify equipment pressure ratings match the refrigerant in use
Memory trick: Match your gauge to the gas — mismatched pressure means glass could pass (burst).
Approved Duct Sealants
Flip cardOnly UL 181-listed tapes and mastics are approved for sealing ductwork joints; ordinary cloth duct tape is prohibited.
- UL 181B-FX = listed tape for flex duct.
- Mastic + mesh used for larger gaps or seams.
- Cloth duct tape dries out and fails within a few years.
Memory trick: Cloth tape cracks, mastic sticks.
Evaporator Delta T
Flip cardThe temperature drop between return air and supply air across the evaporator coil, used as a quick diagnostic indicator of system performance.
- Normal split range is about 16–22°F
- Depends on indoor humidity and airflow (CFM per ton)
- Abnormal splits point to airflow, charge, or coil problems
Memory trick: Twenty degrees means 'twenty-twenty' airflow vision — system's fine!
Cracked Heat Exchanger Detection
Flip cardA cracked heat exchanger allows flue gases like CO to enter the supply air; testing supply air CO levels with the blower running is the most reliable confirmation method.
- Blower operation can pull gases through the crack (negative pressure effect)
- Visual inspection alone often misses hairline cracks
- Elevated supply-air CO confirms exchanger leakage
- Furnace should be shut down and tagged if confirmed
Memory trick: Blower on, CO detector out — that's how cracks get found.
Refrigeration Cycle Order
Flip cardThe four major components of a basic vapor-compression system operate in a fixed sequence to move heat from indoors to outdoors.
- Compressor raises pressure/temperature of vapor
- Condenser rejects heat and condenses gas to liquid
- Metering device drops pressure before evaporator
- Evaporator absorbs heat and boils liquid to vapor
Memory trick: Compress, Condense, Meter, Evaporate — CCME keeps it straight.
Window Orientation Solar Gain
Flip cardSolar heat gain through windows varies by orientation and time of day; west-facing glass typically drives peak afternoon cooling loads.
- West windows peak with afternoon sun
- East windows peak in morning
- South gain is highest in winter, moderate in summer at low sun angle
Memory trick: West is worst for afternoon heat.
Manifold Gas Pressure
Flip cardThe regulated gas pressure at the burner manifold, typically 3.5 in. W.C. for natural gas and 10-11 in. W.C. for propane.
- Measured with a manometer at the gas valve tap
- Incorrect pressure causes under/overfiring and poor combustion
- Set per manufacturer nameplate specifications
Memory trick: Natural gas: three-point-five; propane: eleven.
Heat Anticipator Setting
Flip cardA small adjustable resistor inside a mechanical thermostat that must be set to the actual amperage of the heating control circuit to properly time the thermostat's cycling.
- Measured with a clamp-on ammeter in series with the control circuit
- Setting too high causes overshoot; too low causes short cycling
- Not used on electronic/digital thermostats
Memory trick: Match the amp, avoid the cramp (short cycling).
Plenum Sizing by Velocity
Flip cardSupply plenum cross-sectional area is calculated by dividing system airflow (CFM) by the maximum recommended velocity to prevent noise and pressure loss.
- Area (sq ft) = CFM ÷ Velocity (fpm)
- Typical max plenum velocity ~700-900 fpm
- Undersized plenums increase static pressure and noise
Memory trick: Divide the flow by the speed to find the space you need.
Coil Pressure Drop
Flip cardThe difference between static pressure entering and leaving the evaporator coil, used to detect airflow restrictions such as dirty coils or clogged filters when compared to manufacturer specifications.
- Pressure drop = entering pressure − leaving pressure
- Compare measured drop to manufacturer's rated maximum
- Excessive drop often indicates dirty coil, filter, or restricted airflow
Memory trick: Subtract the readings, compare to spec — restriction you'll detect.
Range Hood Makeup Air
Flip cardCMC requirement that kitchen exhaust systems rated 400 CFM or greater must be provided with a makeup air source to prevent house depressurization.
- Threshold is 400 CFM per CMC
- Prevents backdrafting of gas water heaters/furnaces
- Makeup air can be passive or mechanically supplied and interlocked with the hood
Memory trick: Four hundred's the line — bring in makeup air time.
Cal/OSHA CO PEL
Flip cardCal/OSHA establishes a permissible exposure limit of 25 ppm for carbon monoxide as an 8-hour time-weighted average, stricter than the federal 50 ppm PEL.
- California PEL: 25 ppm (8-hr TWA)
- Federal OSHA PEL: 50 ppm (8-hr TWA)
- CO is colorless, odorless, and produced by incomplete combustion
Memory trick: California cuts it to twenty-five.
Zoning Bypass Duct Sizing
Flip cardIn zoned systems, a bypass duct is sized to handle the difference between total blower airflow and the airflow delivered when only partial zones are open, preventing excessive static pressure.
- Bypass CFM = Total system CFM − Open zone CFM
- Prevents blower overload when zones close
- Oversized bypass can cause temperature control issues
Memory trick: Bypass carries what the closed zones refuse.
TXV vs Fixed Orifice
Flip cardA thermostatic expansion valve modulates refrigerant flow to maintain constant superheat, while a fixed orifice has a set opening optimized for only one condition.
- TXV uses a sensing bulb to respond to evaporator outlet temperature
- Fixed orifice is a non-adjustable, fixed-size opening
- TXV performs better across variable load and outdoor temperature swings
- Both require proper charge for accurate superheat/subcooling readings
Memory trick: TXV = Tracks and adjusts; fixed orifice = fixed and forgetful.
Deep Vacuum Evacuation
Flip cardThe process of removing air and moisture from a refrigeration system using a vacuum pump until the system reaches 500 microns or below, verified with a micron gauge.
- Standard compound gauges cannot accurately measure deep vacuum levels
- 500 microns is the widely accepted industry target before charging
- A rising micron reading after pump shutoff (decay) indicates a leak or moisture
Memory trick: Five hundred microns or bust — dry system is a must.
Low-Voltage Short Diagnosis
Flip cardA repeatedly blown transformer fuse immediately upon reconnecting thermostat wiring usually indicates a short circuit in the low-voltage wiring or a shorted component.
- Test transformer output before connecting wires
- Bare wires touching grounded metal cause shorts
- Isolate wires one at a time to find the short
- Never bypass a fuse with foil or jumper
Memory trick: Fuse pops the instant wires connect? Somewhere there's a short circuit connect.
Evaporator Function
Flip cardThe evaporator coil absorbs heat from indoor air by boiling low-pressure liquid refrigerant into vapor.
- Located on the indoor (or low-pressure) side of the system
- Refrigerant enters as a low-pressure liquid/vapor mix and leaves as superheated vapor
- Heat absorption here is the actual 'cooling' effect felt indoors
Memory trick: Evaporator = Absorbs heat, like a sponge soaking up warmth
CAZ Worst-Case Depressurization Test
Flip cardA safety test that measures pressure in the combustion appliance zone under worst-case exhaust conditions, compared against manufacturer spillage limits for atmospherically vented appliances.
- Typical safe limit for atmospheric appliances is around -3 to -5 Pa depending on manufacturer/testing protocol.
- Exceeding the limit indicates backdraft/spillage risk of carbon monoxide.
- Corrective actions include makeup air, reducing exhaust CFM, or appliance venting changes.
Memory trick: Too much suck, appliance backdraft luck runs out.
Reclaimed vs. Recycled Refrigerant
Flip cardRecycled refrigerant is cleaned on-site for reuse by the same owner; reclaimed refrigerant is processed off-site to AHRI 700 purity standards for resale to other owners.
- Recycling: on-site, same system/owner, minimal processing
- Reclaiming: certified facility, AHRI 700 purity, required for resale/change of ownership
- EPA requires reclamation whenever refrigerant changes ownership
Memory trick: Recycle for yourself, Reclaim to sell
EPA Leak Repair Threshold
Flip cardAppliances with 50+ lbs of refrigerant charge exceeding a specified annual leak rate must be repaired within 30 days under EPA regulations.
- Comfort cooling/other appliances: 15% threshold
- Industrial process refrigeration: 30-35% threshold
- Applies to appliances with 50 lbs or more full charge
Memory trick: 50 lbs, 15% — fix it fast, or face the blast (of fines)
Duct Friction Rate Calculation
Flip cardFriction rate = (Available Static Pressure ÷ Total Effective Length) × 100, expressed in inches of water column per 100 feet of duct, and used to select duct sizes from Manual D tables.
- TEL includes straight duct plus fitting equivalent lengths
- Lower friction rate generally means larger required duct size
- Result is used with airflow (CFM) on a duct sizing chart
Memory trick: Divide the pressure by the path, then scale to a hundred.
Motor Branch-Circuit Protection (175% Rule)
Flip cardNEC 440.22(A) limits the maximum branch-circuit protective device for a single motor-compressor to 175% of its rated-load current (RLA), unless that size is insufficient to handle starting current, in which case it may be increased up to 225%.
- Formula: Max breaker = RLA × 1.75
- Round down to nearest standard size unless 175% isn't sufficient
- May increase up to 225% if needed for starting current
Memory trick: 175% keeps the breaker from tripping on startup surge.
Three-Phase Motor Rotation Reversal
Flip cardThe direction of rotation of a three-phase motor is determined by phase sequence; swapping any two of the three line leads reverses rotation direction.
- Three-phase motors have no capacitors for starting
- Rotation depends on phase sequence (e.g., L1-L2-L3 vs L1-L3-L2)
- Swap only two leads—swapping all three has no effect
Memory trick: Swap two, spin true.
SEER2 Testing Standard
Flip cardSEER2 is an updated efficiency rating standard using a revised test procedure (M1) with higher external static pressure to better reflect real-world duct system resistance.
- Effective for equipment manufactured starting January 1, 2023
- Uses 0.5 in. w.c. static pressure vs. 0.1 in. w.c. under old SEER
- SEER2 values are typically slightly lower than equivalent SEER values
- Applies to central air conditioners and heat pumps
Memory trick: SEER2 pressure tests reality, not a lab fantasy.
HERS Verification & CF3R Form
Flip cardTitle 24 requires certain energy features, including duct leakage, to be field-verified by a certified HERS rater and documented on the CF3R compliance form, separate from the contractor's CF2R installation certificate.
- CF2R = installation certificate (contractor)
- CF3R = verification certificate (HERS rater)
- Duct leakage is a HERS-verified measure under Title 24
Memory trick: 'Contractor installs (CF2R), rater verifies (CF3R).'
Envelope Heat Loss Formula
Flip cardManual J calculates conductive heat loss through building assemblies using Q = U × A × ΔT, where U is the assembly's U-factor, A is area, and ΔT is the design temperature difference.
- Q = U × A × ΔT
- U-factor is the inverse of total R-value
- ΔT uses 99% heating design temperature, not average winter temp
Memory trick: U times Area times Delta-T equals heat that flees.
CO Detector Placement
Flip cardCarbon monoxide detectors should be installed near sleeping areas, away from vents and dead-air pockets, since CO mixes with air rather than settling at floor or ceiling level.
- CO density ~ same as air (slightly lighter)
- Avoid corners, humid areas (bathrooms), and near supply registers
- Install near each sleeping area per most jurisdictions
Memory trick: CO mixes like fog—spread evenly, avoid dead air corners.
Balance Point & Auxiliary Heat
Flip cardThe outdoor temperature at which a heat pump's output equals the building's heat loss; below this point, supplemental heat is needed to maintain comfort.
- Below balance point, heat pump capacity declines with dropping outdoor temp
- Auxiliary heat (electric strips or gas furnace) supplements, not replaces, the heat pump
- Emergency heat mode is a manual override that uses only auxiliary heat
Memory trick: Below the balance, call for backup — strips join in when it's cold enough to hiccup.
Combustion Air Sizing — Horizontal Ducts
Flip cardWhen combustion air is supplied via horizontal ducts to outdoors, each of two required openings must provide 1 sq in of free area per 2,000 Btu/h of total appliance input.
- Vertical ducts/openings direct to outdoors: 1 sq in per 4,000 Btu/h
- Horizontal ducts: 1 sq in per 2,000 Btu/h (double the vertical requirement)
- Applies to EACH of the two openings, not combined
Memory trick: Horizontal ducts work harder — half the ratio, double the size.
Return Duct Leakage Impact
Flip cardReturn-side duct leaks in hot or unconditioned spaces draw outside air into the system under negative pressure, increasing cooling load and reducing delivered capacity, unlike supply-side leaks which simply waste conditioned air.
- Return ducts operate under negative pressure
- Leaks there pull in unconditioned air, not lose conditioned air
- Return leaks in hot attics significantly raise cooling load
Memory trick: Return sucks in the heat; supply just leaks it out.
Non-Condensable Gases
Flip cardGases like air or nitrogen that remain in vapor form inside the refrigeration system and add extra pressure that doesn't correspond to refrigerant saturation temperature.
- Usually caused by improper or incomplete evacuation
- Causes head pressure higher than the PT chart predicts
- Fixed by proper deep vacuum evacuation before charging
Memory trick: Air won't condense — it just adds pressure and offends.
Static Pressure Budget
Flip cardTotal external static pressure (ESP) available from the blower must be divided among all system components (coil, filter, ductwork); remaining pressure after non-duct losses is the friction budget for the duct system.
- Available ESP = blower rated ESP
- Subtract fixed component losses (coil, filter) first
- Remaining ESP is allocated to supply + return duct friction per Manual D
Memory trick: Total pressure minus coil minus filter equals what the ducts get to spend.
Capacitor Discharge Safety
Flip cardCapacitors store electrical energy even when disconnected from power and must be safely discharged before handling to prevent shock injury.
- Use an insulated resistor, not a screwdriver, to discharge
- Capacitors can hold charge for hours after power-off
- Always verify zero charge with a multimeter before touching terminals
- Shock hazard exists even with the disconnect open
Memory trick: Power off doesn't mean charge is gone — discharge before you carry on.
Locked Rotor Amps (LRA) Diagnosis
Flip cardLRA is the current a compressor motor draws when its rotor cannot turn (starting or stalled); sustained current at this level indicates a seized or locked compressor.
- RLA = normal running current; LRA = stall current, much higher
- Brief LRA spike at startup is normal
- Continuous LRA-level draw with humming signals mechanical lockup
Memory trick: Stuck at LRA too long means the rotor's in a locked-up song.
Manual J Load Calculation
Flip cardAn ACCA-approved method for calculating a building's heating and cooling loads room-by-room, based on construction, climate, orientation, and occupancy.
- Produces Btu/hr heating and cooling loads
- Required before Manual S equipment selection
- Considers insulation, windows, infiltration, and internal gains
Memory trick: J is for 'Just how much heat does this house need?'
Venting Categories I-IV
Flip cardNFGC classification of gas appliance venting based on vent pressure (positive/negative) and flue gas condition (condensing/non-condensing).
- Category I: negative pressure, non-condensing (standard furnace)
- Category III: positive pressure, non-condensing (power vented)
- Category IV: positive pressure, condensing (high-efficiency PVC vent)
Memory trick: I is old and lazy (negative draft, dry gas); IV is new and wet (positive, condensing).
Sight Glass Bubbles
Flip cardBubbles in the liquid line sight glass indicate flash gas forming in the liquid line, typically caused by low refrigerant charge or a restriction.
- Clear sight glass = properly subcooled liquid
- Bubbles = flash gas from undercharge or restriction
- Some systems have no sight glass on zeotropic blends
Memory trick: Bubbles mean trouble — low charge or blockage.
Gas Pipe Sizing (cfh Conversion)
Flip cardGas pipe sizing tables require flow demand in cubic feet per hour (cfh), calculated by dividing the appliance's Btu/h input by the fuel's heating value (typically ~1,000 Btu/cf for natural gas).
- Natural gas heating value averages ~1,000-1,100 Btu per cubic foot
- Propane has a much higher heating value (~2,500 Btu/cf), requiring different cfh calculations
- Pipe size also depends on total developed length and allowable pressure drop (commonly 0.5 in w.c.)
Memory trick: Divide Btu load by heating value to get flow.
Hot Surface Igniter (HSI)
Flip cardAn electronic ignition device that heats a ceramic element to a high temperature to ignite the gas-air mixture directly, replacing standing pilots.
- Made of silicon carbide or silicon nitride
- Very fragile — avoid touching with bare skin (oils cause failure)
- Common on modern 80%+ and 90%+ AFUE furnaces
Memory trick: Hot rod glows, gas flows.
Condensate Trap
Flip cardA water-seal trap installed in the condensate drain line of condensing furnaces to prevent positive-pressure flue gases from venting through the drain.
- Required on all Category IV (condensing) furnaces
- Must be primed with water before startup
- Failure to install can allow flue gas leakage or drain blockage from soot
Memory trick: No trap, gas escapes — think sink P-trap.
Altitude Derate for Gas Appliances
Flip cardA code-based adjustment reducing gas furnace input rating by approximately 4% per 1,000 ft of elevation above 2,000 ft to compensate for reduced oxygen density.
- Baseline elevation for standard orifice sizing is sea level to 2,000 ft
- Reduction typically applied via smaller orifice size, not just derated rating on paper
- Manufacturer's high-altitude kit or orifice tables should be consulted for exact values
Memory trick: Every thousand feet past two thousand, shave four percent.
Low Water Cutoff (LWCO)
Flip cardA safety control on a hydronic boiler that senses water level and shuts off the burner if water drops below a safe operating level, preventing dry-fire damage.
- Required by code on most hot water and steam boilers
- Can be float-type or electronic probe-type
- Should be tested periodically per manufacturer instructions
Memory trick: No water, no fire — cutoff saves the boiler.
Flame Rectification
Flip cardA safety method where a flame sensor rod uses the flame's ionized gases to allow a small one-directional DC current to flow, proving flame presence to the control board.
- Typical minimum signal is 1-3 microamps DC
- Oxidation/carbon buildup is the most common failure cause
- Clean with fine emery cloth, not sandpaper (can leave residue)
Memory trick: Dirty rod, dead current, dead flame.