CSLB C-20 HVAC ContractorHeating SystemsMedium

A technician is troubleshooting a furnace that ignites briefly then shuts off after a few seconds, displaying a flame sensing fault code. Testing the flame sensor with a microammeter during burner operation shows only 0.5 microamps DC, below the minimum required. What does this most likely indicate?

  1. AThe high-limit switch is stuck open
  2. BThe transformer secondary voltage is too low
  3. CThe flame sensor rod is coated with oxidation and needs cleaning
  4. DThe gas valve regulator is set too high
Show answer & explanation

Correct answer: C. The flame sensor rod is coated with oxidation and needs cleaning

Flame rectification sensors rely on a clean metal rod contacting the flame to generate a weak DC microamp signal that proves flame presence to the control board. A carbon or oxide coating insulates the rod, reducing the signal below the control's minimum threshold (typically 1-2 microamps), causing nuisance lockouts. Cleaning the rod with fine emery cloth restores proper current flow.

Why the other options are wrong

  • A. A stuck-open high limit would prevent the blower or shut down heat differently, not produce a low flame-sense reading.
  • B. Low transformer voltage would affect gas valve or control operation broadly, not specifically the microamp flame signal.
  • D. Gas pressure issues would affect flame size/quality but not directly cause a low microamp reading from sensor coating.

Flame Rectification

A safety method where a flame sensor rod uses the flame's ionized gases to allow a small one-directional DC current to flow, proving flame presence to the control board.

  • Typical minimum signal is 1-3 microamps DC
  • Oxidation/carbon buildup is the most common failure cause
  • Clean with fine emery cloth, not sandpaper (can leave residue)

Memory trick: Dirty rod, dead current, dead flame.

More Heating Systems questions