CSLB C-20 HVAC ContractorVentilation and Air DistributionMedium

A client is installing a kitchen range hood rated at 500 CFM. Per the California Mechanical Code, what additional requirement is triggered by exceeding the 400 CFM threshold?

  1. AA secondary duct must be run to the attic for pressure relief
  2. BMakeup air must be provided to compensate for the exhausted air
  3. CThe hood must be downgraded to comply with energy code
  4. DA carbon monoxide detector must be installed in the kitchen
Show answer & explanation

Correct answer: B. Makeup air must be provided to compensate for the exhausted air

The CMC requires makeup air whenever a kitchen exhaust hood is rated at or above 400 CFM, preventing excessive negative pressure that could cause backdrafting of combustion appliances or infiltration issues.

Why the other options are wrong

  • A. Attic venting is not a recognized makeup air solution.
  • C. Energy code does not require downgrading hood capacity for this issue.
  • D. CO detectors are a separate life-safety requirement, not tied to this CFM threshold.

Range Hood Makeup Air

CMC requirement that kitchen exhaust systems rated 400 CFM or greater must be provided with a makeup air source to prevent house depressurization.

  • Threshold is 400 CFM per CMC
  • Prevents backdrafting of gas water heaters/furnaces
  • Makeup air can be passive or mechanically supplied and interlocked with the hood

Memory trick: Four hundred's the line — bring in makeup air time.