CSLB C-20 HVAC ContractorCooling and RefrigerationMedium

A technician charges a residential split system on an 85°F day but notices head pressure is significantly higher than the pressure-temperature chart predicts for that ambient temperature, even after verifying correct charge weight. What is the most likely cause?

  1. AThe system is undercharged
  2. BThe evaporator coil is dirty and restricting airflow
  3. CNon-condensable gases, such as air, are trapped in the system
  4. DThe thermostatic expansion valve is overfeeding the evaporator
Show answer & explanation

Correct answer: C. Non-condensable gases, such as air, are trapped in the system

Non-condensable gases like air do not condense in the condenser and add to the total pressure in the system, causing head pressure to read higher than the pressure-temperature chart would predict for a given ambient temperature. This typically results from improper evacuation before charging.

Why the other options are wrong

  • A. Undercharge typically lowers pressures, not raises them abnormally above the chart.
  • B. A dirty evaporator coil reduces airflow and suction pressure but does not typically cause head pressure to deviate from the PT chart.
  • D. An overfeeding TXV would primarily affect superheat and suction pressure, not cause a head pressure/PT chart mismatch.

Non-Condensable Gases

Gases like air or nitrogen that remain in vapor form inside the refrigeration system and add extra pressure that doesn't correspond to refrigerant saturation temperature.

  • Usually caused by improper or incomplete evacuation
  • Causes head pressure higher than the PT chart predicts
  • Fixed by proper deep vacuum evacuation before charging

Memory trick: Air won't condense — it just adds pressure and offends.