CSLB C-20 HVAC ContractorCooling and RefrigerationHard

A technician inspects a system and finds the suction line heavily frosted all the way back to the compressor, with a measured superheat of 0°F. What immediate risk does this condition pose to the compressor?

  1. AThe compressor will experience increased efficiency from super-cooled suction gas
  2. BLiquid refrigerant may enter the compressor, causing slugging and potential mechanical damage
  3. CThe compressor will overheat due to insufficient refrigerant flow
  4. DCompressor amperage draw will drop to near zero
Show answer & explanation

Correct answer: B. Liquid refrigerant may enter the compressor, causing slugging and potential mechanical damage

A superheat of 0°F means the refrigerant leaving the evaporator is still saturated liquid/vapor mixture rather than fully vaporized. This liquid can travel down the suction line to the compressor, causing slugging — a condition where incompressible liquid enters the cylinder or scroll set and causes mechanical damage such as broken valves, reeds, or scroll components.

Why the other options are wrong

  • A. Liquid floodback does not improve efficiency; it risks mechanical failure and can wash oil from bearings.
  • C. Overheating is associated with high superheat (low charge/starved evaporator), not zero superheat.
  • D. Amperage typically stays normal or may fluctuate erratically, not drop to zero, under floodback conditions.

Compressor Flooding/Slugging

A condition where liquid refrigerant returns to the compressor due to insufficient superheat, risking mechanical damage from incompressible liquid entering the compression chamber.

  • Zero or near-zero superheat indicates floodback risk
  • Slugging can break valves, reeds, or scroll sets instantly
  • Suction line accumulators help protect against floodback

Memory trick: Zero superheat, liquid's a threat — slug the compressor, cause regret.