CSLB C-20 HVAC ContractorCooling and RefrigerationMedium

A technician observes continuous bubbles moving through the liquid line sight glass of an operating R-410A split system. What does this most likely indicate?

  1. AAn overcharged condition with excess liquid refrigerant
  2. BExcessive subcooling in the liquid line
  3. CNormal operation expected on all TXV-equipped systems
  4. DLow refrigerant charge or a restriction causing flash gas to form in the liquid line
Show answer & explanation

Correct answer: D. Low refrigerant charge or a restriction causing flash gas to form in the liquid line

A fully liquid-filled line (adequately subcooled) should appear clear in the sight glass. Continuous bubbles indicate the liquid is partially flashing to vapor, typically due to low refrigerant charge or a restriction (e.g., clogged filter drier) causing a pressure drop before the metering device.

Why the other options are wrong

  • A. Overcharge typically produces a clear sight glass with high subcooling, not bubbles.
  • B. Excessive subcooling would produce a clear sight glass, not bubbles.
  • C. Bubbles are not a normal steady-state condition on a properly charged system.

Sight Glass Bubbles

Bubbles in the liquid line sight glass indicate flash gas forming in the liquid line, typically caused by low refrigerant charge or a restriction.

  • Clear sight glass = properly subcooled liquid
  • Bubbles = flash gas from undercharge or restriction
  • Some systems have no sight glass on zeotropic blends

Memory trick: Bubbles mean trouble — low charge or blockage.