CSLB C-20 HVAC ContractorHeating SystemsHard

During a load calculation, a technician must size two permanent combustion air openings using horizontal ducts connecting a mechanical closet directly to outdoors. The closet houses a furnace and water heater with a combined input of 240,000 Btu/h. Per the California Mechanical Code, what is the minimum free area required for EACH opening?

  1. A120 square inches
  2. B100 square inches
  3. C80 square inches
  4. D60 square inches
Show answer & explanation

Correct answer: A. 120 square inches

For horizontal ducts connecting directly to outdoors, the CMC requires 1 square inch of free area per 2,000 Btu/h of total input, applied to EACH of the two openings. 240,000 ÷ 2,000 = 120 square inches per opening.

Why the other options are wrong

  • B. This matches the vertical duct rule (1 in²/2,000... actually vertical uses 4,000) — miscalculated ratio.
  • C. Undersized based on the 1 in²/2,000 Btu/h horizontal duct rule.
  • D. Would correspond to a much smaller input rating.

Combustion Air Sizing — Horizontal Ducts

When combustion air is supplied via horizontal ducts to outdoors, each of two required openings must provide 1 sq in of free area per 2,000 Btu/h of total appliance input.

  • Vertical ducts/openings direct to outdoors: 1 sq in per 4,000 Btu/h
  • Horizontal ducts: 1 sq in per 2,000 Btu/h (double the vertical requirement)
  • Applies to EACH of the two openings, not combined

Memory trick: Horizontal ducts work harder — half the ratio, double the size.