Grid Parameter Verification (Startup)
Flip cardBefore energizing a grid-tied PV system, verifying that the utility grid's voltage and frequency are within the inverter's specified operating limits is crucial for safe synchronization and operation.
- Inverters require stable grid parameters to operate.
- Prevents damage to the inverter from out-of-spec grid conditions.
- Ensures proper synchronization and power quality.
Memory trick: Verify Grid First, Then Energize.
Ladder Overreaching Prevention
Flip cardTo prevent falls, users should never overreach from a ladder. The ladder must be positioned so the worker can comfortably reach the work area without extending beyond the side rails or leaning excessively.
- Maintain your center of gravity between the side rails.
- Reposition the ladder as needed to reach the work.
- Do not lean out or extend arms/tools excessively.
- Overreaching is a major cause of ladder-related injuries.
Memory trick: Ladder's reach has a golden rule: reposition or get a taller tool.
PV Connector Arc Faults
Flip cardElectrical arcs occurring at loose or damaged DC connectors in a PV system, posing a significant fire risk.
- Caused by high resistance or poor contact.
- Generates high heat and can ignite surrounding materials.
- Arc fault circuit interrupters (AFCI) are designed to detect and mitigate these.
Memory trick: Loose connectors spark trouble, literally!
PV String Isc Reduction (Shading)
Flip cardA condition where the short-circuit current of a PV string is significantly lower than expected, often caused by partial shading or module degradation, while open-circuit voltage remains relatively normal.
- Shading primarily impacts current (Isc).
- Open-circuit voltage (Voc) is less affected by shading than Isc.
- Bypass diodes can help, but cannot fully restore current lost to shading.
Memory trick: Voc vs. Isc: Voltage is Open, Current is Short
Confined Space Oxygen Deficiency
Flip cardAn oxygen-deficient atmosphere in a confined space (below 19.5% oxygen) is an Immediately Dangerous to Life or Health (IDLH) condition requiring ventilation before entry.
- Normal oxygen range: 19.5% - 23.5%.
- Oxygen deficiency can cause unconsciousness, death.
- Ventilation is the primary control method.
- Respirators (other than SCBA) are ineffective for oxygen deficiency.
Memory trick: Low O2, ventilate anew, before you go through.
Hazardous Material Spill Response (Initial)
Flip cardThe immediate initial response to a hazardous material spill, especially of corrosive substances, is to prioritize personal safety by evacuating, notifying authorities/supervisors, and isolating the area.
- Prioritize 'Protect Yourself First'.
- Evacuate the immediate area.
- Notify supervisor/emergency services.
- Prevent unauthorized entry to the spill zone.
Memory trick: See the spill? Flee, call, and stand still!
PV String Current Reduction (Shading)
Flip cardIn a series PV string, partial shading on one or more modules will reduce the total string current (Isc) to the level of the lowest current-producing module in that string.
- Series circuits are current-limited by the weakest element.
- Shading drastically reduces module current output.
- Bypass diodes can mitigate this by shunting current around shaded modules.
Memory trick: Series current is like a chain; the weakest link (shade) breaks the gain.
Grid Fault Error
Flip cardAn inverter error indicating a problem with the connection to, or conditions of, the utility grid.
- Prevents inverter from feeding power to the grid.
- Can be caused by open AC disconnects, utility outages, or incorrect grid parameters.
- Requires verifying AC connections and utility status.
Memory trick: Grid Fault means check the 'AC-side' first, from inverter to meter!
Rapid Shutdown Verification (Startup)
Flip cardBefore fully energizing a grid-tied PV system, especially during startup, the functionality of all rapid shutdown devices must be verified to ensure the array can be quickly de-energized to safe voltage levels for emergency personnel.
- Mandated by NEC 690.12 for first responder safety.
- Ensures quick voltage reduction on the PV array.
- Verification typically involves activating the shutdown mechanism and confirming voltage drop.
- A critical safety check before full operation.
Memory trick: Safety First: Rapid Shutdown Must Be Verified.
Cal/OSHA Roof Fall Protection Slope
Flip cardCal/OSHA requires fall protection for employees working on roofs with a slope greater than 4:12 (vertical to horizontal ratio).
- Slope greater than 4:12 requires fall protection.
- Guardrails, safety nets, or personal fall arrest systems are common methods.
- Applies to all roofing work where fall hazards exist.
Memory trick: Four-to-Twelve: Fall Protection is the Rule to Thrive.
PV String Voltage Sizing
Flip cardThe process of selecting the correct number of PV modules in series to match the voltage operating window of a specific inverter or charge controller.
- Open-circuit voltage (Voc) is additive in series.
- Voltage must stay within inverter's min/max operating range.
- Temperature significantly affects Voc (Voc increases at colder temperatures).
Memory trick: Series = Voltage, Parallel = Current
N95 Respirator Use
Flip cardAn N95 respirator is a NIOSH-approved filtering facepiece respirator that filters at least 95% of airborne particles (non-oil-based), used for protection against dusts, mists, and biological aerosols.
- Requires fit-testing for proper seal.
- Not for gases or vapors.
- Must be part of a comprehensive respiratory protection program.
Memory trick: N-95 for dust and bugs, keeps your lungs safe from airborne hugs!
Conduit Heat Effects on PV Wiring
Flip cardConductors routed through conduits, especially metal conduits exposed to direct sunlight, can experience elevated temperatures that accelerate insulation degradation and reduce current carrying capacity.
- Sunlight heats conduit, transferring heat to conductors.
- High temperatures reduce conductor ampacity.
- Excessive heat causes insulation to become brittle and crack.
Memory trick: Hot Conduits Cook Insulation.
Inverter Voltage Rise
Flip cardThe phenomenon where the voltage at the inverter's output terminals increases above the utility's nominal voltage, typically due to impedance in the AC interconnection circuit when power is being exported.
- Caused by resistance in AC wiring, breakers, or utility infrastructure.
- Leads to 'High Grid Voltage' errors and inverter shutdowns.
- Mitigated by proper conductor sizing and minimizing circuit length.
Memory trick: High Grid Voltage? The 'AC Resistance Roadblock' is the culprit!
Fixed PV Tilt Angle Optimization
Flip cardSelecting the best stationary angle for PV modules to maximize annual energy yield, often approximated by the site's latitude.
- Tilt angle affects solar irradiance interception.
- Latitude is a common starting point for fixed tilt.
- Adjustments can be made for seasonal prioritization (e.g., more winter or summer production).
Memory trick: Latitude's your guide for annual gain, but seasons shift the sun's domain!
Bypass Diode Failure (Shorted)
Flip cardA bypass diode failing in a short-circuit condition, effectively bypassing a portion of the PV module cells and reducing the module's output voltage.
- Reduces module voltage contribution.
- Can lead to reduced string Voc and power output.
- Often difficult to detect without IV curve tracing or individual module testing.
Memory trick: Low Voc? Check for 'Bypassed Blocks' or bad connections!
NEC Rooftop Conduit Temperature Adder
Flip cardAn additional temperature value (33°C/60°F) mandated by NEC 310.15(B)(2)(c) to be added to the ambient temperature for conductor ampacity calculations when conduits are mounted close to sun-exposed rooftops.
- Applies to conduits exposed to direct sunlight.
- Conduit must be less than 7/8 inch from roof surface.
- Adder is 33°C (60°F).
- Prevents conductor overheating.
Memory trick: Rooftop heat, 33 degrees to beat, or your wires will meet defeat!
Expansion Tank Placement (Solar Water Heater)
Flip cardThe correct installation location for an expansion tank in a potable solar water heating system, as mandated by plumbing codes, to manage thermal expansion.
- Installed on the cold water inlet side.
- Between shutoff valve/check valve and water heater.
- Absorbs thermal expansion of potable water.
Memory trick: Expansion tank: cold side it must be, between the valve and the heater, you see!
T&P Valve Purpose
Flip cardA safety device required on water heaters and storage tanks to relieve excessive temperature and pressure, preventing tank rupture and ensuring safety.
- Mandated by UPC/CPC.
- Protects against over-temperature and over-pressure.
- Prevents catastrophic tank failure/rupture.
Memory trick: T&P valve: too hot, too much pressure, it's the tank's last measure!
Toxic Non-Potable/Potable Cross-Separation
Flip cardCPC requires a minimum 6-inch vertical and 12-inch horizontal separation between toxic non-potable fluid lines and potable water lines they cross.
- Prevents cross-contamination of drinking water.
- Applies to toxic heat transfer fluids.
- Referenced in CPC Section 603.2.1.
Memory trick: Toxic Pipes: Six Up, Twelve Across for Potable Peace.
NEC 120% Rule (PV Interconnection)
Flip cardA National Electrical Code rule (705.12(B)(2)(3)) that permits the sum of the ampere ratings of all overcurrent devices supplying power to a busbar to exceed the busbar's rating, provided the sum does not exceed 120% of the busbar's rating.
- Applies to load-side PV interconnections.
- Allows for PV systems without service upgrade.
- Maximum combined sources = 120% of busbar rating.
Memory trick: One twenty percent, the busbar's extent, for PV power, heaven-sent!
NEC Rapid Shutdown Time
Flip cardThe maximum time allowed by NEC 690.12 for controlled conductors outside the PV array boundary to be de-energized to safe voltage and power levels after rapid shutdown initiation.
- Mandated by NEC 690.12.
- 30 seconds maximum time.
- Target: ≤30V and ≤240VA outside array boundary.
Memory trick: Rapid shutdown's time is thirty, so first responders stay safe and dirty!
PV OCPD Sizing
Flip cardOvercurrent protection devices for PV array conductors must be sized at 125% of the maximum circuit current to account for continuous operation.
- NEC 690.8(B) applies.
- Ensures device can handle sustained loads.
- Prevents nuisance tripping and ensures safety.
Memory trick: PV OverCurrent Protection: Always Boost by a Quarter.
Potable Water Heater PRV Max Setting
Flip cardThe maximum pressure relief valve setting for a potable water heater, as per CPC, is 150 psi, unless manufacturer specifications dictate a lower value.
- Ensures safety and prevents tank rupture.
- Applies to domestic hot water systems.
- Referenced in CPC Section 504.4 (UPC 504.4).
Memory trick: Pressure Relief Valve: 150 is the Max Safe Threshold.
NEC EGC Sizing (Structure)
Flip cardThe National Electrical Code (NEC) requirement for determining the minimum size of the equipment grounding conductor (EGC) for PV array metallic support structures based on the system's overcurrent protective device rating.
- Uses NEC Table 250.122.
- Ensures a safe fault current path.
- Protects against electric shock and equipment damage.
Memory trick: Grounding size depends on the protector's power.
Rooftop Conduit Temp Adder
Flip cardNEC Table 310.15(B)(2)(a) (now 310.15(B)(1)) requires temperature adders for conductors in raceways on or above rooftops exposed to sunlight, with 33°C (60°F) being common for surface-mounted conduits.
- Accounts for solar heat gain.
- Increases conductor operating temperature.
- Reduces conductor ampacity, requiring larger wire sizes.
Memory trick: Rooftop Wires: Add 60 Degrees Fahrenheit for Safety's Light.
PV Disconnecting Means Purpose
Flip cardThe main safety function of a readily accessible, lockable, and labeled PV system disconnecting means, as required by the NEC.
- Provides a way to de-energize the PV system.
- Crucial for safety during maintenance or emergencies.
- Must be readily accessible, lockable, and labeled.
Memory trick: The PV disconnect is the safety stop, for workers to maintain or for emergencies to drop.
PV AC Disconnect Location
Flip cardThe main AC disconnecting means for a PV system must be readily accessible on the building exterior or within sight of the service entrance equipment, per NEC 690.15(A).
- Crucial for emergency shutdown.
- Must be visible and lockable.
- Ensures safety for first responders and utility workers.
Memory trick: AC Disconnect: Outside or Eye-Level with Service.
BESS Working Clearance
Flip cardNEC Article 706.7(C) requires a minimum 36-inch (900 mm) working clearance in front of battery energy storage systems with exposed live parts.
- Ensures safe access for maintenance.
- Applies to energized parts.
- Critical for preventing electrical hazards.
Memory trick: Battery Systems: Keep 3 Feet Clear for Safety.
CEC PV Supply-Side Connection Length
Flip cardThe maximum permitted length of supply-side PV output circuit conductors from the PV disconnect to the service disconnecting means before overcurrent protection is required at the point of connection, as per CEC.
- Applies to supply-side PV connections.
- Limit is 10 feet.
- Exceeding 10 feet requires overcurrent protection at the connection point.
Memory trick: Ten feet is the golden rule for PV supply-side length, or else protection's due.
NEC Conductor Sizing (PV)
Flip cardThe process of determining the minimum required ampacity for PV circuit conductors, involving continuous load adjustment (125%) and temperature correction factors (NEC Tables 310.16 & 310.15(B)(2)(a)).
- PV output is a continuous load (125% factor).
- Ambient temperature affects ampacity (correction factors).
- Conductor insulation type determines base ampacity column.
Memory trick: Continuous load first, then temperature's curse; size it right, or you'll disperse!
NEC EGC Sizing
Flip cardThe process of determining the minimum required size for an equipment grounding conductor (EGC) based on the rating of the overcurrent protective device, as specified in NEC Table 250.122.
- Based on overcurrent device rating.
- Ensures proper fault current path.
- Table 250.122 is the primary reference.
Memory trick: Grounding conductor size depends on the fuse; check the table, you can't lose!
NEC 120% Rule Calculation
Flip cardA calculation method (from NEC 705.12(B)(2)(3)) to determine the maximum allowable PV inverter output overcurrent device rating when connecting to the load-side of a service panel, based on the busbar and main OCPD ratings.
- Formula: (Busbar Rating × 1.2) - Main OCPD Rating.
- Result is maximum PV OCPD rating.
- Ensures busbar is not overloaded by combined sources.
Memory trick: Busbar times 1.2, minus the main, equals PV's gain!
PV Source Circuit Max Current (Imc)
Flip cardThe maximum circuit current for PV source circuits is calculated by multiplying the module's short-circuit current (Isc) by 125%, as per NEC 690.8(A)(1).
- Accounts for potential overcurrent conditions.
- Used before applying continuous load factors for OCPD sizing.
- Ensures conductors and components are adequately rated.
Memory trick: PV Max Current: Isc Plus a Quarter More.
NEC PV Supply-Side Connection Distance
Flip cardThe maximum allowable physical distance from the utility service conductors' termination point at the service equipment where a PV system's supply-side connection can be made, as per NEC 705.11(A).
- Applies to supply-side PV interconnections.
- Ensures short, protected connections.
- Aids in emergency disconnect procedures.
Memory trick: Keep the solar connection close to the main power heart.
T&P Discharge Pipe Termination Height
Flip cardCPC Section 504.6.4 mandates that a T&P relief valve discharge pipe terminate not more than 6 inches above the receptor for visual inspection.
- Ensures early detection of valve activation.
- Prevents water damage from hidden leaks.
- Applies to potable water heater systems.
Memory trick: T&P Discharge: Six Inches Max for a Clear View.
NEC BESS Working Clearance
Flip cardThe minimum unobstructed space required by the National Electrical Code (NEC 110.26) in front of a Battery Energy Storage System (BESS) or other electrical equipment containing live parts for safe access, examination, and maintenance.
- Applies to equipment requiring access while energized.
- Ensures worker safety.
- Minimum depth is 36 inches for most common voltages.
Memory trick: Give live parts three feet of freedom to work safely.
PV Array Structure Bonding
Flip cardThe NEC-mandated process of electrically connecting all non-current-carrying metal parts of a PV array structure to ensure a continuous and low-impedance path to the grounding electrode system.
- Required by NEC 690.43 and 250.110.
- Uses listed bonding jumpers or devices.
- Ensures safety by providing a fault current path.
Memory trick: Bonding the array, don't delay, for safety's path, come what may!
NEC PV AC Output Circuit Continuous Current
Flip cardThe National Electrical Code (NEC) requirement to calculate the continuous current for PV AC output circuit conductors at 125% of the inverter's maximum continuous output current rating to account for continuous operation.
- Applies to AC output conductors from PV inverters.
- Uses a 125% multiplier for continuous current.
- Ensures conductors are adequately sized for sustained operation.
Memory trick: Solar AC needs 125% more respect for continuous flow.
Non-Potable Solar Thermal Cross-Contamination
Flip cardUPC/CPC requirements to prevent heat transfer fluids from non-potable solar thermal systems from contaminating the potable water supply, primarily through backflow prevention or air gaps.
- Non-potable fluids can be toxic.
- Requires backflow prevention devices.
- Or an approved air gap with indirect waste receptor.
- Critical for public health.
Memory trick: Non-potable fluids, a backflow device intrudes, or an air gap, no more rude!
CPC Non-Potable/Potable Separation
Flip cardThe minimum distance required by the California Plumbing Code between piping carrying non-potable fluid and piping carrying potable water.
- Applies to solar thermal systems with non-potable fluids.
- Prevents cross-contamination.
- Ensures public health and safety.
Memory trick: Clean water needs a little space to stay safe.
GFDI Device Function (PV)
Flip cardA safety device required by NEC 690.5 in PV systems to detect ground-fault currents and rapidly de-energize the affected circuit, mitigating fire and shock hazards.
- Required in PV systems by NEC 690.5.
- Detects ground-fault currents.
- Interrupts the circuit to prevent fire and shock.
Memory trick: GFDI: ground faults it will find, and dangers it will bind!
Non-Potable Expansion Tank Pressure Rating
Flip cardExpansion tanks for non-potable closed-loop systems must have a maximum working pressure rating of at least 1.25 times the system's maximum working pressure, per CPC 1008.3.
- Ensures tank integrity under pressure spikes.
- Applies to solar thermal space heating or process heat.
- Critical safety requirement.
Memory trick: Expansion Tank: One and a Quarter Times the System's Pressure.
PV Disconnect Actuations
Flip cardNEC 690.17 limits PV system disconnecting means to a maximum of six movements or operations to de-energize the system.
- Ensures quick shutdown for safety.
- Applies to both AC and DC disconnects.
- Can be individual switches or breakers in a group.
Memory trick: Disconnect in Six or Less, for Safety's Success.
Potable Water & Drain Separation
Flip cardMinimum separation distances required by UPC/CPC between potable water piping and building drains or sewers to prevent cross-contamination.
- 6 inches horizontal separation.
- 2 inches vertical separation (when crossing).
- Crucial for public health and safety.
Memory trick: Six horizontal, two vertical, keeps your water safe and ethical!
Drainback System Piping Design
Flip cardSpecific requirements for collector loop piping in a solar thermal drainback system to ensure complete fluid drainage.
- All piping must be continuously sloped.
- Prevents freezing and stagnation by draining collectors when pump is off.
- Requires careful attention to eliminate sags or traps.
Memory trick: For drainback's flow, a continuous slope must show, let no water stay, let it all go!
Pump Noise/Vibration Causes
Flip cardCommon issues leading to undesirable noise and vibration in hydronic circulation pumps.
- Air in the system is a primary culprit.
- Can also be caused by cavitation, misalignment, or mechanical wear.
- Requires systematic troubleshooting for resolution.
Memory trick: When the pump makes a ruckus and a hum, check for air, it's often the drum!
NTC Thermistor Behavior
Flip cardA type of thermistor whose electrical resistance decreases as its temperature increases.
- Commonly used as temperature sensors in solar thermal controllers.
- Provides an inversely proportional relationship between resistance and temperature.
- Essential for accurate temperature measurement and system control.
Memory trick: NTC: Negative temp means resistance drops, when the heat just pops!
Optimal PV Tilt Angle (Fixed Array)
Flip cardFor a fixed-tilt PV array, the optimal tilt angle for maximizing annual energy production is generally equal to the site's latitude, as this balances seasonal solar exposure.
- Tilt angle = Latitude for annual optimization.
- Steeper angles (Latitude + 15°) favor winter production.
- Shallower angles (Latitude - 15°) favor summer production.
- Consideration for snow shedding may influence tilt in some climates.
Memory trick: Latitude's Light Leverages Long-term Luster.
PV Shading Mitigation (Complex Sites)
Flip cardFor PV sites with extensive and unavoidable shading, effective mitigation involves using module-level power electronics (MLPE) to optimize individual module performance and carefully designing the array layout to minimize the impact of shade on system output.
- MLPE (microinverters/optimizers) allows individual modules to operate independently.
- Prevents shaded modules from reducing the output of the entire array.
- Strategic array layout (e.g., splitting arrays, adjusting spacing) minimizes shade impact.
- Shade analysis tools are critical for identifying optimal placement and mitigation strategies.
Memory trick: Complex Conundrums? Choose Clever Component Control and Careful Configuration.
Gantt Chart (Project Management)
Flip cardA Gantt chart is a project management tool that provides a visual overview of a project schedule, displaying tasks, their durations, start and end dates, and dependencies, often highlighting the critical path.
- Visually represents project tasks and timelines.
- Shows task dependencies (which tasks must finish before others start).
- Helps identify the critical path (sequence of tasks that determines project duration).
- Useful for planning, scheduling, and monitoring project progress.
Memory trick: Gantt's Great for Grasping Grand Goals Gracefully.
Air Binding in Solar Thermal
Flip cardAir binding occurs when air pockets become trapped in the solar thermal piping, preventing the circulation of heat transfer fluid and severely reducing system efficiency.
- Common during initial fill or after maintenance.
- Symptoms include pump running with little or no heat transfer and low collector temperatures.
- Requires proper purging procedures to resolve.
Memory trick: Air in the pipes, heat takes a hike.
Differential Controller Short Cycling
Flip cardShort cycling occurs when a solar thermal pump rapidly turns on and off, often due to control issues, sensor inaccuracies, or hydraulic problems, reducing efficiency and component lifespan.
- Can be caused by air in sensor wells or collectors.
- Incorrect differential settings or sensor placement are also culprits.
- Leads to increased wear on the pump and reduced system performance.
Memory trick: Erratic readings, pump's a-leaping.
Immersion Temperature Sensor Accuracy
Flip cardFor accurate temperature readings, an immersion-type sensor's sensing element (bulb) must be fully and consistently immersed in the fluid it is designed to measure. Incomplete immersion leads to inaccurate, erratic, or delayed readings.
- Sensing element must be completely surrounded by the fluid.
- Partial immersion can cause readings influenced by ambient air or stratification.
- Check water level and sensor placement during troubleshooting.
- Erratic readings are a strong indicator of incomplete immersion or poor contact.
Memory trick: Sensor Needs Full Contact.
Secure Power Supply (SPS) Inverter
Flip cardA Secure Power Supply (SPS) or PV-direct backup feature in a grid-tied inverter allows for a dedicated outlet to provide limited, non-battery-backed AC power directly from the PV array during a grid outage, as long as the sun is shining.
- Provides emergency power during grid outages without batteries.
- Power is available only when the sun is shining.
- Typically limited to a single dedicated outlet or small load center.
- Does not provide whole-home backup.
Memory trick: Solar Power During Shutdowns? Secure Power Supply is the Smart Solution.
PV System Grounding & Bonding
Flip cardConnecting all non-current-carrying metallic components of a PV system to the earth to provide a safe path for fault currents and prevent electrocution.
- Mandated by NEC Article 690.
- Protects against shock hazards and lightning strikes.
- Ensures proper overcurrent protection device operation.
Memory trick: Ground your frames, or feel the pain! Safety first, come sun or rain!
Value Engineering in PV
Flip cardValue engineering in PV system design and estimating is a systematic process to improve the value of a project by optimizing the balance between function, performance, quality, safety, and cost, often by identifying alternative solutions or materials.
- Focuses on function and value, not just initial cost.
- Identifies less expensive alternatives that meet performance criteria.
- Involves cross-functional team analysis.
- Aims for the lowest lifecycle cost, not just lowest upfront cost.
Memory trick: Value Verification Varies by Viable Vendor's Value-Engineering Vision.
Solar DHW Heat Exchanger Code
Flip cardCode requirements for heat exchangers separating non-potable solar fluids from potable water prioritize public health and safety, typically mandating double-wall vented designs.
- Prevents contamination of drinking water.
- Double-wall provides redundant separation.
- Venting or a leak detection system indicates failure of the inner wall.
Memory trick: Double walls, vented space, keeps the glycol in its place.
Solar Thermal Piping Materials
Flip cardMaterials used for solar thermal piping must withstand high temperatures and pressures, especially near collectors, and be compatible with heat transfer fluids.
- Copper is a common choice due to high temperature and pressure tolerance.
- Plastic pipes (PVC, PEX, CPVC) have lower temperature limits and are generally unsuitable for collector loops.
- Stainless steel or specialized high-temperature flexible tubing may also be used.
Memory trick: High heat, high pressure, copper's the treasure.
Collector Header Pitch
Flip cardThe slight slope applied to horizontal piping (headers) in a solar thermal collector array to facilitate fluid drainage and air purging.
- Crucial for preventing stagnation and air binding.
- Ensures complete drainage when the system is shut down or for maintenance.
- Standard minimum is 1/8 inch per foot.
Memory trick: To drain the pipes and clear the air, 1/8 inch per foot, beyond compare.