A solar contractor is installing a new PV system on a residential property. The inverter output circuit is rated at 25A. The conductors for this circuit will be run in a conduit through an attic space where the ambient temperature can reach 45°C (113°F). The conductors used are copper with 90°C insulation. According to the National Electrical Code (NEC), what is the minimum required ampacity for these conductors after applying temperature correction and continuous load adjustments?
- A25A
- B43.75A
- C38.75A
- D31.25A
Show answer & explanationAnswer & explanation
Correct answer: D. 31.25A
First, the continuous load adjustment: PV inverter output is a continuous load, so the circuit's overcurrent protection must be sized at 125% of the continuous current (25A * 1.25 = 31.25A). This means the conductors must have an ampacity of at least 31.25A *before* temperature correction. Next, temperature correction: For 90°C conductors in 45°C ambient, NEC Table 310.15(B)(2)(a) (formerly 310.16) shows a temperature correction factor of 0.82. To achieve a required ampacity of 31.25A after correction, the conductor's ampacity from the table must be 31.25A / 0.82 = 38.11A. Looking at 90°C column in NEC Table 310.16: 10 AWG copper is 40A. So, 31.25A is the minimum required ampacity *after* all adjustments.
Why the other options are wrong
- A. 25A is the inverter output, but conductors must be sized for 125% continuous load and then corrected for temperature.
- B. 43.75A is too high and not the correct minimum required ampacity.
- C. 38.75A is not a standard calculation result and does not represent the minimum required ampacity after all adjustments.
NEC Conductor Sizing (PV)
The process of determining the minimum required ampacity for PV circuit conductors, involving continuous load adjustment (125%) and temperature correction factors (NEC Tables 310.16 & 310.15(B)(2)(a)).
- PV output is a continuous load (125% factor).
- Ambient temperature affects ampacity (correction factors).
- Conductor insulation type determines base ampacity column.
Memory trick: Continuous load first, then temperature's curse; size it right, or you'll disperse!