CSLB C-46 Solar ContractorPhotovoltaic System InstallationMedium

A solar installer is connecting a new 7.6 kW string inverter to a 240V, 30A dedicated circuit in a residential service panel. According to NEC 690.8(A)(1), what is the minimum required ampacity for the conductors connecting the inverter's AC output to the overcurrent protective device?

  1. A20 Amperes
  2. B40 Amperes
  3. C25 Amperes
  4. D30 Amperes
Show answer & explanation

Correct answer: B. 40 Amperes

NEC 690.8(A)(1) requires that the ampacity of conductors for PV inverter output circuits be at least 125% of the maximum current. For a 7.6 kW inverter at 240V, the maximum current is 7600W / 240V = 31.67A. Applying the 125% rule: 31.67A * 1.25 = 39.59A. Therefore, a 40A conductor ampacity is required.

Why the other options are wrong

  • A. 20A is too low for the calculated current.
  • C. 25A is too low and does not meet the 125% rule.
  • D. 30A is the breaker size, not the conductor ampacity, and is insufficient for the 125% rule.

NEC 690.8(A)(1) 125% Rule

For PV inverter output circuits, the conductor ampacity must be at least 125% of the maximum inverter output current.

  • Applies to continuous loads.
  • Ensures conductors can safely handle sustained current.
  • Calculated current is multiplied by 1.25.

Memory trick: Current's high, so multiply by one point twenty-five (1.25) to size the wire right.