Master Electrician Exam (NEC)Load CalculationsMedium

A single-family dwelling unit has a 240V, 40A electric vehicle supply equipment (EVSE) installed. According to NEC 220.57, what is the minimum demand load that must be included for this EVSE in the service calculation?

  1. A9.6 kW
  2. B8 kW
  3. C12 kW
  4. D19.2 kW
Show answer & explanation

Correct answer: A. 9.6 kW

According to NEC 220.57, the demand load for electric vehicle supply equipment (EVSE) shall be calculated at 100% of the nameplate rating of the EVSE. The nameplate rating is derived from the voltage and current: 240V * 40A = 9600 VA or 9.6 kW.

Why the other options are wrong

  • B. This option might misinterpret the voltage or current rating, or apply an incorrect demand factor.
  • C. This option might be a common incorrect demand factor or a miscalculation.
  • D. This option likely doubles the load, which is incorrect for EVSE calculations.

EVSE Demand Load (NEC 220.57)

Electric Vehicle Supply Equipment (EVSE) loads are always calculated at 100% of their nameplate rating for feeder and service calculations.

  • Applies to all EVSE installations.
  • No demand factors are permitted for EVSE loads.
  • Calculated at 100% of the equipment's rated current or power.

Memory trick: EVSE: Electric Vehicle, Straight-up Exact.