Master Electrician Exam (NEC)Load CalculationsMedium
A master electrician is calculating the feeder demand load for a commercial building. The building has 10 general-purpose receptacle outlets, each rated for 15A, 120V. According to NEC 220.44, what is the minimum demand load for these receptacles?
- A1,000 VA
- B180 VA
- C12,000 VA
- D1,800 VA
Show answer & explanationAnswer & explanation
Correct answer: A. 1,000 VA
According to NEC 220.44, for receptacle loads in other than dwelling units, the demand factor is 100% for the first 10 kVA and 50% for the remainder. Each receptacle is considered to have a minimum load of 180 VA. For 10 receptacles, the total calculated load is 10 * 180 VA = 1800 VA. Since this is less than 10 kVA (10,000 VA), the demand factor is 100%, resulting in a demand load of 1800 VA.
Why the other options are wrong
- B. This value would be incorrect as it only considers one receptacle, not the demand factor application.
- C. This value is significantly higher than the NEC requirements for this scenario and does not reflect the correct calculation method.
- D. This is the correct calculation: 10 receptacles * 180 VA/receptacle = 1800 VA. Since this is less than 10 kVA, the demand factor is 100%.
Commercial Receptacle Demand (NEC 220.44)
For receptacle loads in other than dwelling units, each 15A or 20A general-purpose receptacle outlet is calculated at not less than 180 VA. A demand factor is then applied based on the total calculated load.
- Each 15A or 20A general-purpose receptacle = 180 VA
- First 10 kVA of total calculated receptacle load = 100% demand factor
- Remainder of total calculated receptacle load = 50% demand factor
- Applies to commercial and industrial settings, not dwelling units
Memory trick: Commercial plugs demand 180 VA each, then a 10kVA 100% rule kicks in.