Master Electrician Exam (NEC)Load CalculationsMedium

A master electrician is performing an optional method load calculation for a single-family dwelling (NEC 220.82). The dwelling has a total general lighting and receptacle load of 10,000 VA, an electric range of 12 kW, a 5 kW electric water heater, and a 2 kW dishwasher. There is also a 10 kW central electric space heating system. What is the demand load for the electric space heating system using this method?

  1. A10 kW
  2. B5 kW
  3. C6.5 kW
  4. D7.5 kW
Show answer & explanation

Correct answer: A. 10 kW

According to NEC 220.82(C)(5), the largest of the heating or air-conditioning loads is taken at 100% when using the optional method for dwelling units. Since there is only a heating load mentioned, it is taken at its full value.

Why the other options are wrong

  • B. This is incorrect; it applies an incorrect demand factor to the heating load.
  • C. This is incorrect; it applies an incorrect demand factor to the heating load.
  • D. This is incorrect; it applies an incorrect demand factor to the heating load.

Optional Method Heating/A/C Load

When using the optional method (NEC 220.82) for dwelling units, the largest of the electric space heating or air-conditioning loads is included at 100% of its nameplate rating.

  • Applies to dwelling units using the optional calculation method.
  • Only the larger of heating or A/C is considered.
  • The selected load is included at 100% of its rating.
  • This differs from standard method where other demand factors might apply to heating.

Memory trick: Optional heating: No discount, 100% is the count!