Step2Study
ContractorC-10100% Free

CSLB C-10 Electrical Contractor

Practice bank
210 Qs
Real exam
110 Qs
Time limit
210 min
Passing
~72% (scaled; CSLB/PSI)

Exam blueprint

Planning and Estimating
20%
Wiring Methods and Materials
25%
Electrical Theory and Calculations
20%
Equipment and Installation
20%
Safety and Testing
15%

Practice

Untimed · instant feedback · 4 practice tests of 90 questions

Questions per test

Custom practice

Flashcard on every question Mental map when you miss

Exam simulation

4 timed tests · 110 questions each · 210 min · pass 72% · 210 questions in the bank

+50 XP per test · +100 XP for a pass

Random simulation (weighted by domain)

Everything is open to everyone. Create a free account to save scores, XP, badges and get progress emails.

Free study resources

All resources →

Part of a learning path

Study with friends

Challenge a friend to beat your score.

CSLB C-10 Electrical Contractor practice test questions

Sample questions from the 210-question bank, with answers and explanations.

All questions
  1. 1. A 6 AWG THHN copper conductor is installed to feed equipment with terminals rated for 75°C. Per NEC 110.14(C), what ampacity must be used for this conductor even though THHN insulation is rated for 90°C?

    Wiring Methods and Materials

    • A. 55 amps (60°C column)
    • B. 65 amps (75°C column)
    • C. 50 amps
    • D. 75 amps (90°C column)
    Show answer

    B. 65 amps (75°C column)

    NEC 110.14(C) requires conductor ampacity to be selected based on the lowest temperature rating of any connected termination, equipment, or conductor. Since the terminals are rated 75°C, the conductor must be sized using the 75°C column of Table 310.16, which gives 65A for 6 AWG copper, even though the insulation itself is rated 90°C.

  2. 2. A 25-horsepower, 230-volt, 3-phase motor has a Table 430.250 full-load current of 68 amperes. What is the minimum ampere rating required for the motor's disconnecting means switch?

    Equipment and Installation

    • A. 136 amperes
    • B. 78.2 amperes
    • C. 68 amperes
    • D. 85 amperes rounded from 115%
    Show answer

    B. 78.2 amperes

    NEC 430.110(A) requires the disconnecting means for a motor circuit to have an ampere rating of at least 115% of the motor's full-load current: 68A x 1.15 = 78.2A. A disconnect switch rated at least 80A (next standard switch size) would be selected in practice, but the calculated minimum is 78.2A.

  3. 3. A raceway will contain three 4/0 AWG THHN copper service conductors plus one 4 AWG THHN equipment grounding conductor. Using Chapter 9, Table 5 conductor areas (4/0 = 0.3237 in², 4 AWG = 0.0824 in²) and the 40% fill rule, what is the minimum trade size EMT required?

    Wiring Methods and Materials

    • A. 1-1/2 inch
    • B. 3 inch
    • C. 2-1/2 inch
    • D. 2 inch
    Show answer

    D. 2 inch

    Total conductor area = (3 × 0.3237) + 0.0824 = 0.9711 + 0.0824 = 1.0535 in². A 1-1/2-inch EMT allows only 0.814 in² at 40% fill (insufficient). A 2-inch EMT allows 1.342 in² at 40% fill, which comfortably exceeds the 1.0535 in² required, making it the minimum acceptable size.

  4. 4. A homeowner asks an electrician to add a new 20-ampere, 120-volt receptacle circuit to serve small kitchen countertop appliances. Per the CEC, what protection must this receptacle have?

    Equipment and Installation

    • A. A dedicated equipment ground only, no special protection required
    • B. Surge protection device (SPD) at the panel
    • C. AFCI protection only
    • D. GFCI protection
    Show answer

    D. GFCI protection

    CEC/NEC 210.8(A)(6) requires GFCI protection for all 125-volt, 15- and 20-ampere receptacles installed to serve kitchen countertop surfaces in dwelling units.

  5. 5. An electrician installs NM-B cable into a metal single-gang device box equipped with an internal cable clamp. Per NEC 334.30, within what maximum distance from the box must the cable be secured to a framing member?

    Wiring Methods and Materials

    • A. 18 inches
    • B. 12 inches
    • C. 8 inches
    • D. 6 inches
    Show answer

    B. 12 inches

    NEC 334.30 requires NM cable to be secured within 12 inches of every box, cabinet, or fitting where a cable clamp is used, and at intervals not exceeding 4.5 feet thereafter. This prevents strain on terminations and protects the cable from mechanical damage.

  6. 6. A run of EMT conduit contains several 90-degree bends and offsets installed between two pull points. According to NEC 358.26, what is the maximum total number of degrees of bend permitted between pull points?

    Wiring Methods and Materials

    • A. 360°
    • B. 450°
    • C. 270°
    • D. 180°
    Show answer

    A. 360°

    NEC 358.26 limits the total bends in an EMT run between pull points (such as boxes or conduit bodies) to 360 degrees, equivalent to four 90-degree bends, to allow conductors to be pulled without excessive damage.

  7. 7. A homeowner asks why standard Type MC cable cannot be buried directly underground without additional protection. Which characteristic of standard MC cable explains this limitation?

    Wiring Methods and Materials

    • A. MC cable lacks an equipment grounding conductor entirely
    • B. The interlocked metal armor is not watertight or corrosion-resistant for direct burial
    • C. MC cable cannot carry more than 20 amperes
    • D. MC cable conductors are limited to 60°C insulation ratings
    Show answer

    B. The interlocked metal armor is not watertight or corrosion-resistant for direct burial

    Standard Type MC cable has an interlocked metallic armor that is not sealed against moisture and is subject to corrosion, so it is unsuitable for direct burial or wet locations unless specifically listed and jacketed for that use.

  8. 8. A single-phase, dry-type transformer rated 4.5 kVA has a 480-volt primary. The calculated primary full-load current is 9.4 amperes. Per NEC Table 450.3(B), since the primary current exceeds 9 amperes, the maximum primary overcurrent protection allowed is 125% of FLC. What is the maximum standard primary overcurrent device rating permitted?

    Equipment and Installation

    • A. 12 amperes
    • B. 20 amperes
    • C. 10 amperes
    • D. 15 amperes
    Show answer

    D. 15 amperes

    125% x 9.4A = 11.75A. Since this does not correspond to a standard overcurrent device size, NEC 450.3(B) and 240.6(A) permit rounding up to the next higher standard rating, which is 15 amperes.

  9. 9. A 100-ampere circuit breaker protects a copper feeder circuit. According to NEC Table 250.122, what is the minimum size copper equipment grounding conductor required for this circuit?

    Wiring Methods and Materials

    • A. 8 AWG
    • B. 10 AWG
    • C. 4 AWG
    • D. 6 AWG
    Show answer

    A. 8 AWG

    NEC Table 250.122 sizes the equipment grounding conductor based on the rating of the overcurrent device protecting the circuit, not the actual load. For overcurrent protection rated up to 100A, the minimum copper EGC size is 8 AWG.

  10. 10. Six 10 AWG THWN copper conductors must be installed in a single EMT raceway. Using NEC Chapter 9, Annex C, Table C.1 (EMT conductor fill for over two conductors), what is the minimum trade size EMT required?

    Wiring Methods and Materials

    • A. 1-1/4 inch
    • B. 1/2 inch
    • C. 1 inch
    • D. 3/4 inch
    Show answer

    D. 3/4 inch

    NEC Annex C Table C.1 lists the maximum number of conductors permitted in EMT trade sizes. For 10 AWG THWN, 1/2 inch EMT permits only 4 conductors, while 3/4 inch EMT permits 8 conductors. Since 6 conductors exceed the 1/2 inch capacity but fit within 3/4 inch, the minimum trade size is 3/4 inch.

  11. 11. An electrician installs EMT into a service panel through a concentric knockout, securing it with a single locknut and bushing. A licensing inspector requires a bonding jumper be added. Why is this necessary?

    Wiring Methods and Materials

    • A. Bonding jumpers are required on every raceway regardless of knockout type
    • B. The panel is undersized for the number of circuits installed
    • C. EMT is never permitted to terminate directly into service equipment
    • D. Concentric knockouts can leave paint or a poor electrical connection, preventing reliable bonding through the ring alone
    Show answer

    D. Concentric knockouts can leave paint or a poor electrical connection, preventing reliable bonding through the ring alone

    Where concentric or eccentric knockouts are punched, the reduced material in the rings may not provide a reliable low-impedance path to ground. NEC 250.92(B) requires bonding jumpers or bonding-type locknuts/bushings in these cases to ensure an effective ground-fault current path at service equipment.

  12. 12. During a service equipment installation, a raceway knockout is larger than the connector, requiring the use of reducing washers. Per NEC 250.92(B), what additional measure is required to maintain a reliable equipment grounding path at service equipment?

    Wiring Methods and Materials

    • A. Reducing washers are prohibited in all electrical installations
    • B. An additional ground rod must be driven at that enclosure
    • C. Double locknuts alone are sufficient without further bonding
    • D. A bonding jumper must be installed to bypass the reducing washers
    Show answer

    D. A bonding jumper must be installed to bypass the reducing washers

    NEC 250.92(B) does not recognize reducing washers, oversized knockouts with locknuts alone, or standard locknuts/bushings as reliable bonding methods at service equipment. When reducing washers are used, a bonding jumper must be installed to ensure a low-impedance path for fault current, since normal threaded connections cannot be relied upon there.

  13. 13. According to NEC 362.10, in which of the following locations may Electrical Nonmetallic Tubing (ENT) be installed without additional protective measures?

    Wiring Methods and Materials

    • A. Exposed on the exterior wall of a building where subject to physical damage
    • B. Direct buried in earth without concrete encasement
    • C. Inside a spray booth classified as a hazardous location
    • D. Concealed within a masonry wall of a building three stories or less in height
    Show answer

    D. Concealed within a masonry wall of a building three stories or less in height

    ENT is a flexible, corrugated nonmetallic raceway intended for concealed use in walls, floors, and ceilings of buildings not exceeding three floors above grade. It is not permitted in exposed locations subject to physical damage, direct burial without concrete encasement, or in hazardous locations.

  14. 14. An engineer specifies two 3/0 AWG THHN copper conductors per phase, installed in parallel in separate conduits, to serve a 400A load. Each 3/0 AWG THHN conductor has an adjusted allowable ampacity of 225A. What is the total allowable ampacity of the parallel conductor set per phase, per NEC 310.10(H)?

    Wiring Methods and Materials

    • A. 337.5 amps
    • B. 225 amps
    • C. 450 amps
    • D. 400 amps
    Show answer

    C. 450 amps

    When conductors are installed in parallel under NEC 310.10(H), they must be identical in length, material, size, insulation, and termination, and the total ampacity equals the sum of each individual conductor's ampacity. Two 225A conductors in parallel yield 225A + 225A = 450A, which is sufficient to serve the 400A load.

  15. 15. A 208V three-phase feeder supplies a continuous 50A load located 200 feet from the panel, wired with 8 AWG copper conductors (16,510 circular mils). Using the formula VD = (√3 × K × I × D) / CM, where K = 12.9 ohms·cmil/ft for copper, what is the approximate voltage drop, and does it comply with the recommended 3% (6.24V) limit?

    Wiring Methods and Materials

    • A. 13.5V, exceeds the limit
    • B. 6.2V, complies
    • C. 9.8V, exceeds the limit
    • D. 3.1V, complies
    Show answer

    A. 13.5V, exceeds the limit

    VD = (1.732 × 12.9 × 50 × 200) / 16,510 ≈ (1.732 × 12.9 = 22.34; 22.34 × 50 = 1,117; 1,117 × 200 = 223,400; 223,400 / 16,510 ≈ 13.5V). Since 13.5V far exceeds the recommended 3% limit of 6.24V (208V × 0.03), the 8 AWG conductors are undersized for this run and a larger conductor is needed.

  16. 16. A homeowner wants a new 120-volt, 20-ampere receptacle installed on the exterior wall of the dwelling near the patio. What type of protection is required for this receptacle per the CEC?

    Equipment and Installation

    • A. GFCI protection only
    • B. No special protection required if the receptacle is within 6 feet of grade
    • C. AFCI protection only
    • D. Both AFCI and GFCI protection combined
    Show answer

    A. GFCI protection only

    NEC 210.8(A)(3) requires GFCI protection for all 125-volt, 15- and 20-ampere receptacles installed outdoors at dwelling units, regardless of height above grade.

  17. 17. A contractor is installing wiring for equipment inside a paint spray booth classified as a Class I, Division 1 hazardous location due to flammable vapors present under normal operating conditions. Which wiring method is required for this area per NEC Article 501?

    Equipment and Installation

    • A. Nonmetallic-sheathed cable (Romex) in surface raceway
    • B. Rigid metal conduit (RMC) or intermediate metal conduit (IMC) with threaded, explosion-proof sealed fittings
    • C. Electrical metallic tubing (EMT) with standard set-screw fittings
    • D. Metal-clad cable (MC) with standard connectors
    Show answer

    B. Rigid metal conduit (RMC) or intermediate metal conduit (IMC) with threaded, explosion-proof sealed fittings

    NEC 501.10(A) requires that wiring methods in Class I, Division 1 locations be threaded rigid metal conduit or threaded intermediate metal conduit, with boxes, fittings, and joints made explosion-proof and sealed per 501.15 to prevent ignition of flammable vapors.

  18. 18. A single-gang metal device box contains two 12/2 NM-B cables (4 current-carrying 12 AWG conductors, 2 grounds) with no internal cable clamps, and will hold one duplex receptacle. Using NEC box fill rules where each 12 AWG conductor counts as 2.25 cubic inches, what is the minimum required box volume?

    Wiring Methods and Materials

    • A. 15.75 cubic inches
    • B. 18.0 cubic inches
    • C. 13.5 cubic inches
    • D. 20.25 cubic inches
    Show answer

    A. 15.75 cubic inches

    Conductors: 4 × 2.25 = 9.0. Grounding conductors (all count as one, based on largest): 1 × 2.25 = 2.25. Device yoke (counts as two volume allowances, based on largest conductor): 2 × 2.25 = 4.5. Total = 9.0 + 2.25 + 4.5 = 15.75 cubic inches.

  19. 19. A ladder-type cable tray is 18 inches wide and will contain multiple single-conductor Type XHHW cables sized 1000 kcmil, each 1.2 inches in diameter. Per NEC 392.22(A)(1), for single conductors sized 1000 kcmil and larger, the sum of the cable diameters must not exceed the tray width. What is the maximum number of these cables permitted in the tray?

    Wiring Methods and Materials

    • A. 21
    • B. 12
    • C. 15
    • D. 18
    Show answer

    C. 15

    The sum of cable diameters cannot exceed the tray width: 18 in ÷ 1.2 in per cable = 15 cables. Any additional cable would cause the total diameter sum to exceed the 18-inch tray width, violating the rule for large single-conductor cables in cable tray.

  20. 20. An electrician installs a straight run of EMT conduit along an exposed wall in a commercial building. According to the NEC, EMT must be securely fastened within 3 feet of each outlet box and at what maximum interval along the remaining run?

    Wiring Methods and Materials

    • A. Every 8 feet
    • B. Every 6 feet
    • C. Every 10 feet
    • D. Every 12 feet
    Show answer

    C. Every 10 feet

    NEC 358.30 requires EMT to be securely fastened within 3 feet of every outlet box, junction box, cabinet, or termination, and at intervals not exceeding 10 feet along the remaining length of the run.

  21. 21. An electrician terminates aluminum THHN conductors onto a device that is listed and rated for use with aluminum conductors (marked AL-CU). What additional step should be taken at the termination to help prevent oxidation and ensure a reliable long-term connection?

    Wiring Methods and Materials

    • A. Increase the conductor size by two AWG sizes to compensate
    • B. Wrap the termination with electrical tape only
    • C. Use only push-in style connections for aluminum conductors
    • D. Apply an approved antioxidant compound to the conductor before making the connection
    Show answer

    D. Apply an approved antioxidant compound to the conductor before making the connection

    Aluminum conductors form an oxide layer when exposed to air, which increases resistance and heat at terminations. Manufacturers and the NEC recommend applying an approved antioxidant compound during termination on devices listed for aluminum use to maintain a low-resistance, reliable connection.

  22. 22. A dwelling service is supplied by 400 kcmil copper THHN service-entrance conductors. Per NEC Table 250.66, what is the minimum size copper grounding electrode conductor (GEC) required?

    Wiring Methods and Materials

    • A. 4 AWG copper
    • B. 2 AWG copper
    • C. 2/0 AWG copper
    • D. 1/0 AWG copper
    Show answer

    D. 1/0 AWG copper

    NEC Table 250.66 specifies that for copper service-entrance conductors larger than 350 kcmil through 600 kcmil, the minimum copper grounding electrode conductor size is 1/0 AWG. Since 400 kcmil falls within this range, a 1/0 AWG copper GEC is required.

  23. 23. An electrician examines a metal-jacketed cable that contains a thin aluminum bonding strip running the full length inside the spiral metal armor, providing supplemental grounding continuity along with the armor itself. This describes which cable type?

    Wiring Methods and Materials

    • A. Type NM cable
    • B. Type MC cable
    • C. Type SE cable
    • D. Type AC cable
    Show answer

    D. Type AC cable

    Type AC (armored) cable includes an internal aluminum bonding strip in contact with the spiral steel armor to ensure a low-impedance grounding path, as required by NEC 320.108. MC cable instead typically includes a separate, full-sized insulated or bare equipment grounding conductor rather than relying on a thin bonding strip.

  24. 24. A 12-inch length of 1/2-inch EMT nipple connects two enclosures and contains four 12 AWG THHN conductors (each 0.0133 in² per NEC Chapter 9 Table 5). The 1/2-inch EMT has an internal area of 0.304 in². What is the correct fill rule that applies to this nipple, and does the total conductor area comply?

    Wiring Methods and Materials

    • A. Nipples always require the standard 40% fill limit, making this installation non-compliant
    • B. Nipples are exempt from all fill calculations regardless of length
    • C. The 60% exception only applies to nipples over 24 inches, so 40% fill must be used here
    • D. Nipples 24 inches or less allow 60% fill with no adjustment factors; conductor area (0.0532 in²) is well under the 0.1824 in² limit, so it complies
    Show answer

    D. Nipples 24 inches or less allow 60% fill with no adjustment factors; conductor area (0.0532 in²) is well under the 0.1824 in² limit, so it complies

    NEC Chapter 9, Note 4 to the Tables permits conduit or tubing nipples 24 inches or less in length to be filled to 60% of their cross-sectional area without applying the ampacity adjustment factors of 310.15(C)(1). Here, 60% of 0.304 in² = 0.1824 in², and the four 12 AWG THHN conductors total only 0.0532 in², well within the allowed area.

  25. 25. A 400-ampere feeder OCPD supplies tap conductors run in conduit for 8 feet before terminating in a single 40-ampere panelboard. Applying the 10-foot tap rule of NEC 240.21(B)(1), what is the minimum ampacity required for the tap conductors?

    Equipment and Installation

    • A. 400 amperes
    • B. 20 amperes
    • C. 40 amperes
    • D. 100 amperes
    Show answer

    C. 40 amperes

    The 10-foot tap rule requires tap conductor ampacity to be not less than 1/10 of the feeder OCPD rating (400A x 0.10 = 40A) and not less than the rating of the device it supplies (40A panel). Both conditions point to a minimum of 40A, and the 8-foot tap length satisfies the 10-foot maximum requirement.

CSLB C-10 Electrical Contractor flashcards

Tap a card to flip it. 179 flashcards in the full deck.

  • Termination Temperature Limitation

    Flip card

    Conductor ampacity is limited by the lowest temperature rating among the conductor, termination, and equipment, per NEC 110.14(C).

    • 90°C insulation doesn't guarantee 90°C ampacity use
    • Terminals often rated 60°C or 75°C
    • Always use the lowest rating in the circuit path
    Study this card →
  • Motor Disconnect Sizing (430.110)

    Flip card

    The motor disconnecting means must be rated at least 115% of the motor's full-load current for motors rated 600V or less.

    • Applies to the disconnect switch, not the branch-circuit protection
    • Use Table 430.250 (3-phase) or 430.248 (1-phase) for FLC values
    • Distinct from 250% short-circuit protection sizing under 430.52
    Study this card →
  • Mixed Conductor Conduit Fill

    Flip card

    When conductors of different sizes share a raceway, sum their individual cross-sectional areas from Table 5 and compare to the raceway's 40% fill area from Table 4.

    • Sum all conductor areas including the EGC
    • Use 40% fill allowance for 3 or more conductors
    • Round up to the next standard trade size if the total area doesn't fit the smaller size
    Study this card →
  • GFCI in Dwelling Kitchens

    Flip card

    GFCI protection is required for all 125V, 15A/20A receptacles serving kitchen countertop surfaces.

    • NEC 210.8(A)(6) governs dwelling kitchen receptacles
    • GFCI trips on ground-fault current as low as 4-6mA
    • Applies regardless of distance from sink
    Study this card →
  • NM Cable Securing (334.30)

    Flip card

    Type NM cable must be stapled/secured within 12 inches of boxes with clamps and at 4.5-foot intervals along the run.

    • 12 inches from box with clamp
    • 4.5 feet between staples in the run
    • 8-inch exception applies only to single-gang nonmetallic boxes without clamps
    Study this card →
  • Maximum Bends in Raceway

    Flip card

    Raceways such as EMT, IMC, and RMC are limited to 360 degrees of total bend between pull points to allow safe conductor installation.

    • 360° = four 90° bends maximum
    • Applies between pull points (boxes, conduit bodies)
    • Exceeding this makes conductor pulling difficult and risks damage
    Study this card →
  • MC Cable Limitations

    Flip card

    Type MC (Metal-Clad) cable uses an interlocked or smooth metal armor; standard versions are not moisture-sealed and require listing for wet or underground use.

    • Interlocked armor does not prevent water intrusion by design.
    • Special jacketed/listed MC cable is required for wet locations or direct burial.
    • MC cable is common in commercial branch circuits and feeders.
    Study this card →
  • Transformer Primary Protection (450.3(B))

    Flip card

    For transformers 600V or less with primary current 9A or greater, primary-only overcurrent protection may be sized up to 125% of primary FLC, rounded up to the next standard device size if needed.

    • If primary current is less than 9A, up to 167% is permitted
    • If primary current is less than 2A, up to 300% is permitted
    • Rounding to next standard size is allowed per 240.6(A) when 125% doesn't match a standard rating
    Study this card →
  • Equipment Grounding Conductor Sizing (Table 250.122)

    Flip card

    The EGC size for a circuit is based on the rating of the circuit's overcurrent protective device, per NEC Table 250.122, independent of actual conductor ampacity.

    • 60A OCPD → 10 AWG copper
    • 100A OCPD → 8 AWG copper
    • 200A OCPD → 6 AWG copper
    Study this card →
  • Annex C Conduit Fill Tables

    Flip card

    NEC Chapter 9, Annex C provides pre-calculated maximum conductor fill counts for specific raceway types and conductor types, eliminating manual area calculations.

    • Tables apply only when all conductors are the same size and type.
    • Table C.1 is specific to EMT.
    • Using Annex C tables directly is faster than manual 40%/31% fill calculations.
    Study this card →
  • Concentric Knockout Bonding

    Flip card

    NEC 250.92(B) requires bonding jumpers at service equipment where concentric or eccentric knockouts may compromise the reliability of the grounding path.

    • Concentric rings reduce metal thickness, risking poor continuity.
    • Bonding jumpers or listed bonding bushings restore a reliable path.
    • Applies specifically at service equipment enclosures.
    Study this card →
  • Bonding at Service Equipment (250.92B)

    Flip card

    At service equipment, certain connection methods (like reducing washers or oversized knockouts) are not considered reliable for bonding and require a supplemental bonding jumper.

    • 250.92(B) lists acceptable bonding methods at service equipment
    • Reducing washers alone are not an acceptable bonding method there
    • A bonding jumper must bypass unreliable connections to maintain fault current path
    Study this card →
  • Electrical Nonmetallic Tubing (ENT)

    Flip card

    A pliable corrugated raceway used for concealed wiring in buildings of limited height, not for exposed or hazardous applications.

    • Limited to buildings 3 floors or less unless concrete-encased
    • Not permitted exposed to physical damage
    • Prohibited in hazardous locations
    Study this card →
  • Parallel Conductor Ampacity

    Flip card

    Conductors run in parallel per NEC 310.10(H) must match in size, length, and material, with total ampacity equal to the sum of each conductor's individual ampacity.

    • Applies to conductors 1/0 AWG and larger
    • All parallel sets must be identical in every conduit
    • Total ampacity = sum of each conductor's ampacity
    Study this card →
  • Three-Phase Voltage Drop Calculation

    Flip card

    Three-phase voltage drop uses the formula VD = (√3 × K × I × D) / CM, incorporating the square root of 3 factor unique to three-phase circuits.

    • √3 (1.732) factor distinguishes 3-phase from single-phase VD formulas
    • K = 12.9 for copper, 21.2 for aluminum (approximate constants)
    • Recommended max voltage drop is typically 3% for branch circuits/feeders combined 5%
    Study this card →
  • Outdoor Dwelling GFCI

    Flip card

    All 125V, 15/20A receptacles installed outdoors at dwelling units must have GFCI protection.

    • Applies regardless of receptacle height or accessibility
    • Covers patios, balconies, and yard receptacles
    • Part of NEC 210.8(A) dwelling unit GFCI locations list
    Study this card →
  • Class I Division 1 Wiring

    Flip card

    Locations where flammable gases/vapors are present under normal operating conditions require explosion-proof wiring methods per NEC Article 501.

    • Threaded RMC or IMC required per 501.10(A)
    • Seals required per 501.15 to prevent flame/gas propagation
    • Division 2 areas allow some additional wiring methods with restrictions
    Study this card →
  • Box Fill with Device Yoke

    Flip card

    Per NEC 314.16(B), each strap/yoke supporting a device counts as two conductor-volume allowances based on the largest conductor connected to it.

    • Conductors: 1 volume allowance each based on size.
    • All grounds together: 1 allowance based on largest ground.
    • Device yoke: 2 allowances based on largest conductor connected.
    Study this card →
  • Cable Tray Fill for Large Single Conductors

    Flip card

    For single-conductor cables 1000 kcmil and larger, NEC 392.22(A)(1) requires the sum of cable diameters not exceed the cable tray width.

    • Rule applies to conductors 1000 kcmil and larger
    • Sum of diameters ≤ tray width (not area-based)
    • Divide tray width by individual cable diameter to find max count
    Study this card →
  • EMT Support Spacing

    Flip card

    Electrical metallic tubing (EMT) must be securely fastened at regular intervals to prevent sagging and mechanical damage.

    • Support required within 3 ft of each box or termination.
    • Maximum support interval along the run is 10 ft.
    • Applies to NEC Article 358 (EMT).
    Study this card →
  • Aluminum Termination Antioxidant

    Flip card

    Antioxidant compound is applied to aluminum conductor terminations to prevent oxide buildup that increases resistance and heat.

    • Aluminum oxidizes quickly when exposed to air
    • Antioxidant compound maintains low-resistance connections
    • Only use devices listed AL-CU or CO/ALR for aluminum conductors
    Study this card →
  • GEC Sizing per Table 250.66

    Flip card

    The grounding electrode conductor size is based on the size of the largest ungrounded service-entrance conductor, per NEC Table 250.66.

    • Table ranges increase GEC size as service conductor size increases
    • 400 kcmil copper falls in the 350-600 kcmil range
    • Corresponding GEC size is 1/0 AWG copper
    Study this card →
  • AC Cable Bonding Strip

    Flip card

    Type AC cable includes an internal aluminum bonding strip in contact with its spiral metal armor, providing an effective grounding path per NEC 320.108.

    • Distinguishes AC cable from MC cable construction
    • Armor plus bonding strip together serve as the equipment ground
    • MC cable usually has a separate grounding conductor instead
    Study this card →
  • Short Nipple Fill Exception

    Flip card

    Raceway nipples 24 inches or less in length may be filled to 60% of their cross-sectional area, and conductor bundling adjustment factors do not apply.

    • Standard multi-conductor fill limit is 40%
    • Nipples ≤24 inches allow 60% fill
    • No ampacity adjustment factors apply to nipples
    Study this card →

Questions are original practice items written to match the published exam objectives. Step2Study is not affiliated with or endorsed by any certification body.