CSLB C-10 Electrical ContractorWiring Methods and MaterialsHard

A 208V three-phase feeder supplies a continuous 50A load located 200 feet from the panel, wired with 8 AWG copper conductors (16,510 circular mils). Using the formula VD = (√3 × K × I × D) / CM, where K = 12.9 ohms·cmil/ft for copper, what is the approximate voltage drop, and does it comply with the recommended 3% (6.24V) limit?

  1. A13.5V, exceeds the limit
  2. B6.2V, complies
  3. C9.8V, exceeds the limit
  4. D3.1V, complies
Show answer & explanation

Correct answer: A. 13.5V, exceeds the limit

VD = (1.732 × 12.9 × 50 × 200) / 16,510 ≈ (1.732 × 12.9 = 22.34; 22.34 × 50 = 1,117; 1,117 × 200 = 223,400; 223,400 / 16,510 ≈ 13.5V). Since 13.5V far exceeds the recommended 3% limit of 6.24V (208V × 0.03), the 8 AWG conductors are undersized for this run and a larger conductor is needed.

Why the other options are wrong

  • B. 6.2V would comply, but this is not the calculated result for 8 AWG.
  • C. 9.8V understates the actual voltage drop for this run.
  • D. 3.1V is far too low for this length and load with 8 AWG conductors.

Three-Phase Voltage Drop Calculation

Three-phase voltage drop uses the formula VD = (√3 × K × I × D) / CM, incorporating the square root of 3 factor unique to three-phase circuits.

  • √3 (1.732) factor distinguishes 3-phase from single-phase VD formulas
  • K = 12.9 for copper, 21.2 for aluminum (approximate constants)
  • Recommended max voltage drop is typically 3% for branch circuits/feeders combined 5%

Memory trick: Three phases need the root-three factor before you find the drop.

More Wiring Methods and Materials questions