CSLB C-10 Electrical ContractorEquipment and InstallationHard

A single-phase, dry-type transformer rated 4.5 kVA has a 480-volt primary. The calculated primary full-load current is 9.4 amperes. Per NEC Table 450.3(B), since the primary current exceeds 9 amperes, the maximum primary overcurrent protection allowed is 125% of FLC. What is the maximum standard primary overcurrent device rating permitted?

  1. A12 amperes
  2. B20 amperes
  3. C10 amperes
  4. D15 amperes
Show answer & explanation

Correct answer: D. 15 amperes

125% x 9.4A = 11.75A. Since this does not correspond to a standard overcurrent device size, NEC 450.3(B) and 240.6(A) permit rounding up to the next higher standard rating, which is 15 amperes.

Why the other options are wrong

  • A. 12A is not a standard overcurrent device size recognized by 240.6(A).
  • B. 20A skips over the correct next standard size and exceeds what the rule allows.
  • C. 10A is below the calculated 11.75A minimum requirement.

Transformer Primary Protection (450.3(B))

For transformers 600V or less with primary current 9A or greater, primary-only overcurrent protection may be sized up to 125% of primary FLC, rounded up to the next standard device size if needed.

  • If primary current is less than 9A, up to 167% is permitted
  • If primary current is less than 2A, up to 300% is permitted
  • Rounding to next standard size is allowed per 240.6(A) when 125% doesn't match a standard rating

Memory trick: Above 9 amps, 125% is your cap — round up to fill the gap.