CSLB C-10 Electrical ContractorWiring Methods and MaterialsHard

Six 10 AWG THWN copper conductors must be installed in a single EMT raceway. Using NEC Chapter 9, Annex C, Table C.1 (EMT conductor fill for over two conductors), what is the minimum trade size EMT required?

  1. A1-1/4 inch
  2. B1/2 inch
  3. C1 inch
  4. D3/4 inch
Show answer & explanation

Correct answer: D. 3/4 inch

NEC Annex C Table C.1 lists the maximum number of conductors permitted in EMT trade sizes. For 10 AWG THWN, 1/2 inch EMT permits only 4 conductors, while 3/4 inch EMT permits 8 conductors. Since 6 conductors exceed the 1/2 inch capacity but fit within 3/4 inch, the minimum trade size is 3/4 inch.

Why the other options are wrong

  • A. 1-1/4 inch EMT far exceeds what is needed for this conductor count.
  • B. 1/2 inch EMT holds only 4 10 AWG THWN conductors, insufficient for 6.
  • C. 1 inch EMT is larger than necessary for only 6 conductors.

Annex C Conduit Fill Tables

NEC Chapter 9, Annex C provides pre-calculated maximum conductor fill counts for specific raceway types and conductor types, eliminating manual area calculations.

  • Tables apply only when all conductors are the same size and type.
  • Table C.1 is specific to EMT.
  • Using Annex C tables directly is faster than manual 40%/31% fill calculations.

Memory trick: 'Same size, same table' — Annex C works only for uniform conductors.