CSLB C-10 Electrical ContractorEquipment and InstallationMedium

A 25-horsepower, 230-volt, 3-phase motor has a Table 430.250 full-load current of 68 amperes. What is the minimum ampere rating required for the motor's disconnecting means switch?

  1. A136 amperes
  2. B78.2 amperes
  3. C68 amperes
  4. D85 amperes rounded from 115%
Show answer & explanation

Correct answer: B. 78.2 amperes

NEC 430.110(A) requires the disconnecting means for a motor circuit to have an ampere rating of at least 115% of the motor's full-load current: 68A x 1.15 = 78.2A. A disconnect switch rated at least 80A (next standard switch size) would be selected in practice, but the calculated minimum is 78.2A.

Why the other options are wrong

  • A. 200% of FLC applies to short-circuit protection sizing, not the disconnect switch rating.
  • C. This is the FLC itself, without the required 115% safety margin.
  • D. 85A is not the correct calculated value; it misapplies the percentage.

Motor Disconnect Sizing (430.110)

The motor disconnecting means must be rated at least 115% of the motor's full-load current for motors rated 600V or less.

  • Applies to the disconnect switch, not the branch-circuit protection
  • Use Table 430.250 (3-phase) or 430.248 (1-phase) for FLC values
  • Distinct from 250% short-circuit protection sizing under 430.52

Memory trick: 115% keeps the switch safely ahead of the motor's pull.