1. A 6 AWG THHN copper conductor is installed to feed equipment with terminals rated for 75°C. Per NEC 110.14(C), what ampacity must be used for this conductor even though THHN insulation is rated for 90°C?
Wiring Methods and Materials
- A. 55 amps (60°C column)
- B. 65 amps (75°C column)
- C. 50 amps
- D. 75 amps (90°C column)
Show answerAnswer
B. 65 amps (75°C column)
NEC 110.14(C) requires conductor ampacity to be selected based on the lowest temperature rating of any connected termination, equipment, or conductor. Since the terminals are rated 75°C, the conductor must be sized using the 75°C column of Table 310.16, which gives 65A for 6 AWG copper, even though the insulation itself is rated 90°C.