Master Electrician Exam (NEC)Grounding and BondingMedium

A master electrician is installing a new 200A, 120/240V, single-phase service for a residential dwelling. The service entrance conductors are 2/0 AWG copper. The grounding electrode system consists of a metal underground water pipe and a ground rod. What is the minimum size copper grounding electrode conductor required to connect to the metal underground water pipe electrode?

  1. A2 AWG
  2. B6 AWG
  3. C4 AWG
  4. D1/0 AWG
Show answer & explanation

Correct answer: C. 4 AWG

According to NEC Table 250.66, for 2/0 AWG copper service conductors, the minimum size copper grounding electrode conductor is 4 AWG. The connection to the metal underground water pipe must be sized based on this table, without the exceptions applied to ground rods.

Why the other options are wrong

  • A. Incorrect. 2 AWG would be required for larger service conductors (e.g., 3/0 AWG or 4/0 AWG copper).
  • B. Incorrect. 6 AWG is the minimum size for a ground rod electrode, but not for a metal underground water pipe with 2/0 AWG service conductors.
  • D. Incorrect. 1/0 AWG would be required for even larger service conductors (e.g., 250 kcmil copper).

GEC Sizing for Water Pipe Electrode

The grounding electrode conductor (GEC) connected to a metal underground water pipe electrode must be sized according to NEC Table 250.66 based on the largest ungrounded service-entrance conductor, without the size limitations applicable to rod, pipe, or plate electrodes.

  • Sized using Table 250.66.
  • Based on the size of the largest ungrounded service-entrance conductor.
  • Not subject to the 6 AWG copper maximum for ground rods.
  • Must be continuous or spliced per NEC 250.64(C).

Memory trick: Water pipe's GEC size is like a direct current, straight from the table.

More Grounding and Bonding questions