Master Electrician Exam (NEC)Services, Feeders, and Branch CircuitsEasy

A master electrician is installing a new 200A, 120/240V, single-phase service for a dwelling unit. The service entrance conductors are 3/0 AWG copper. What is the minimum size required for the main bonding jumper (MBJ) if it is copper?

  1. A6 AWG
  2. B4 AWG
  3. C2 AWG
  4. D1/0 AWG
Show answer & explanation

Correct answer: B. 4 AWG

According to NEC Table 250.102(C)(1), for service-entrance conductors of 3/0 AWG copper, the minimum size for the main bonding jumper made of copper is 4 AWG.

Why the other options are wrong

  • A. 6 AWG copper is for smaller service entrance conductors, not 3/0 AWG.
  • C. 2 AWG copper is larger than required for 3/0 AWG service entrance conductors.
  • D. 1/0 AWG copper is significantly larger than required for 3/0 AWG service entrance conductors.

Main Bonding Jumper Sizing (NEC 250.102(C)(1))

The main bonding jumper (MBJ) connects the equipment grounding conductor(s) and the service-disconnect enclosure to the grounded conductor of the service, ensuring electrical continuity and fault current path.

  • Sized based on the largest ungrounded service-entrance conductor or equivalent area for parallel conductors.
  • Referenced in NEC Table 250.102(C)(1).
  • Must be copper or aluminum.

Memory trick: Bonding Jumper: Connects the grounds, like a bridge for safety.