Master Electrician Exam (NEC)Grounding and BondingHard

A master electrician is installing a new 480V, 3-phase, 4-wire wye service where the service entrance conductors are 500 kcmil copper. The grounding electrode conductor is connected to a concrete-encased electrode (Ufer ground). What is the minimum size copper grounding electrode conductor required for this connection, according to NEC 250.66(B)?

  1. ANo. 1/0 AWG
  2. BNo. 2 AWG
  3. CNo. 3/0 AWG
  4. DNo. 2/0 AWG
Show answer & explanation

Correct answer: D. No. 2/0 AWG

According to NEC Table 250.66, for service conductors 500 kcmil copper, the minimum size copper grounding electrode conductor (GEC) is No. 1/0 AWG when connected to a ground rod, plate electrode, or water pipe. However, per 250.66(B), if the GEC is connected to a concrete-encased electrode (Ufer), it is permitted to be reduced to No. 2 AWG copper or No. 1/0 AWG aluminum. This reduction is applied to the minimum size from the table. The table shows 1/0 AWG for 500 kcmil, so 2/0 AWG is incorrect. For a concrete-encased electrode, the GEC is not required to be larger than No. 2 AWG copper or No. 1/0 AWG aluminum. The question asks for the minimum size, which would be No. 2 AWG copper for a concrete-encased electrode.

Why the other options are wrong

  • A. No. 1/0 AWG is the minimum size from Table 250.66 for 500 kcmil copper service conductors if connected to a ground rod, but 250.66(B) allows reduction for concrete-encased electrodes.
  • B. No. 2 AWG copper is the maximum required size for a GEC to a concrete-encased electrode, regardless of service conductor size (NEC 250.66(B)). This is the correct answer as it is the minimum required size in this specific scenario.
  • C. No. 3/0 AWG is larger than the maximum permitted for a concrete-encased electrode and is incorrect.

GEC Sizing Exception (Ufer)

When a grounding electrode conductor is connected to a concrete-encased electrode, it is not required to be larger than No. 2 AWG copper or No. 1/0 AWG aluminum, even if Table 250.66 would indicate a larger size.

  • Found in NEC 250.66(B).
  • Applies specifically to concrete-encased electrodes (Ufer grounds).
  • Provides a maximum size, often resulting in a smaller GEC than otherwise calculated.

Memory trick: Ufer ground: GEC no bigger than two.

More Grounding and Bonding questions