Master Electrician Exam (NEC)Grounding and BondingMedium

A master electrician is inspecting a previously installed grounding electrode system for a dwelling. The system includes a metal underground water pipe electrode and a supplemental electrode. The water pipe has 10 feet of contact with the earth. What is the minimum length of the supplemental electrode required if it is a ground rod, according to NEC 250.53(A)(2)?

  1. A8 feet
  2. B10 feet
  3. C6 feet
  4. D4 feet
Show answer & explanation

Correct answer: A. 8 feet

NEC 250.53(A)(2) states that if a metal underground water pipe electrode is used, it must be supplemented by an additional electrode, and the supplemental electrode must comply with 250.52(A)(2) through (A)(8). For a ground rod [250.52(A)(5)], the minimum length driven into the earth is 8 feet.

Why the other options are wrong

  • B. This is the minimum contact length for a water pipe, not a ground rod.
  • C. This is too short for a ground rod electrode.
  • D. This is too short for a ground rod electrode.

Ground Rod Electrode Length

A rod electrode used as part of a grounding electrode system must be a minimum of 8 feet in length and driven fully into the earth.

  • Part of the NEC 250.52(A)(5) requirements.
  • Must be driven to a minimum 8-foot depth.
  • Often used as a supplemental electrode.

Memory trick: Eight feet for the rod, if water pipe's not enough.