Master Electrician Exam (NEC)Grounding and BondingEasy

A master electrician is installing a new 100A, 120/240V, single-phase service for a residential dwelling. The service entrance conductors are No. 1 AWG copper. What is the minimum size copper grounding electrode conductor required if the largest grounding electrode is a ground rod?

  1. ANo. 6 AWG
  2. BNo. 8 AWG
  3. CNo. 4 AWG
  4. DNo. 2 AWG
Show answer & explanation

Correct answer: A. No. 6 AWG

According to NEC Table 250.66, for service conductors No. 1 AWG copper, the minimum size copper grounding electrode conductor (GEC) is No. 6 AWG when connected to a ground rod, plate electrode, or concrete-encased electrode.

Why the other options are wrong

  • B. No. 8 AWG is for smaller service conductors (e.g., up to No. 2 AWG copper service conductors), but not typically for 1 AWG when connected to a rod.
  • C. No. 4 AWG is typically for larger service conductors (e.g., 2/0 AWG to 350 kcmil copper).
  • D. No. 2 AWG is for very large services (e.g., 350 kcmil to 600 kcmil copper).

GEC Sizing (Specific Example)

For No. 1 AWG copper service conductors, the GEC to a ground rod is No. 6 AWG copper.

  • Direct application of NEC Table 250.66.
  • Common residential service size.
  • Ensures adequate fault current path.

Memory trick: Number One service needs Six for the rod.