1. A commercial building has a 480Y/277V, 3-phase, 4-wire electrical service. A new 3-phase motor rated at 20 HP (Horsepower) is being installed. Assuming the motor's full-load current (FLC) for 480V is 27A (from NEC Table 430.250) and a power factor of 0.85, what is the approximate apparent power (kVA) drawn by this motor?
General Electrical Knowledge and Plan Reading
- A. 16.8 kVA
- B. 13.4 kVA
- C. 20.1 kVA
- D. 23.5 kVA
Show answerAnswer
D. 23.5 kVA
Apparent Power (S) for a 3-phase system is calculated as S = (√3 * V_L * I_L) / 1000, where V_L is the line-to-line voltage and I_L is the line current. So, S = (1.732 * 480V * 27A) / 1000 = 22448.64 VA / 1000 = 22.45 kVA. The closest option is 23.5 kVA, as the FLC from the NEC table is a minimum for sizing, and actual motors may draw slightly more, or the options are rounded.