A technician is installing a new 480Y/277V, 3-phase, 4-wire feeder to supply a lighting panel. The panel has a total non-continuous lighting load of 150A per phase. What is the minimum required ampacity for the feeder overcurrent protective device (OCPD), assuming no demand factors or other loads?

  1. A225 A
  2. B150 A
  3. C200 A
  4. D187.5 A
Show answer & explanation

Correct answer: B. 150 A

Since the lighting load is specified as 'non-continuous,' the 125% rule for continuous loads (NEC 215.3 for feeders) does not apply. Therefore, the overcurrent protective device must be sized at least 100% of the non-continuous load. The minimum required ampacity for the OCPD is simply the total non-continuous load, which is 150A.

Why the other options are wrong

  • A. This is an incorrect calculation or unrelated standard size.
  • C. This is a common standard OCPD size, but the calculated minimum is 150A. A 200A OCPD would be permitted if higher than the minimum, but 187.5A is not the minimum.
  • D. This would be 125% of 150A (187.5A), which is incorrect for a non-continuous load.

OCPD Sizing for Non-Continuous Loads

Overcurrent protective devices (OCPDs) for non-continuous loads must have an ampacity not less than 100% of the load served.

  • Non-continuous loads operate for less than 3 hours at a time.
  • This contrasts with continuous loads, which require OCPDs sized at 125% of the load.
  • NEC Articles 210.20(A) for branch circuits and 215.3 for feeders govern OCPD sizing.

Memory trick: OCPD: Continuous 125%, Non-continuous 100%.