Journeyman Electrician Exam (NEC)General Electrical Knowledge and Plan ReadingMedium

A client's industrial facility has a 480V, 3-phase, 3-wire delta electrical service. If a balanced resistive load draws 30A from each line, what is the total apparent power (S) consumed by the load?

  1. A7.2 kVA
  2. B41.6 kVA
  3. C24.9 kVA
  4. D14.4 kVA
Show answer & explanation

Correct answer: C. 24.9 kVA

For a 3-phase system, apparent power (S) = √3 * V_line * I_line. Given V_line = 480V and I_line = 30A. S = √3 * 480V * 30A = 1.732 * 480 * 30 = 24940.8 VA, which is approximately 24.9 kVA.

Why the other options are wrong

  • A. This is likely a result of dividing by √3 or other incorrect calculation.
  • B. This might result from using 3 * V_phase * I_phase or other incorrect 3-phase formula.
  • D. This is calculated as V_line * I_line (single phase) or incorrect use of constants.

3-Phase Apparent Power

Apparent power (S) in a 3-phase system is the product of the line voltage, line current, and the square root of 3. It is measured in Volt-Amperes (VA).

  • S = √3 * V_line * I_line
  • Includes both real and reactive power components.
  • Used for sizing electrical equipment like transformers and generators.

Memory trick: Three-phase power, 'Root Three VI' for apparent, 'Root Three VI Cosine' for real.