Journeyman Electrician Exam (NEC)General Electrical Knowledge and Plan ReadingMedium

A client requires power for a new industrial machine with a nameplate rating of 10 kVA, 3-phase, 480V, and a power factor of 0.8 lagging. What is the approximate real power (kW) drawn by this machine?

  1. A6 kW
  2. B12 kW
  3. C10 kW
  4. D8 kW
Show answer & explanation

Correct answer: D. 8 kW

Real power (P) is calculated by multiplying apparent power (S) by the power factor (PF). So, P = S * PF = 10 kVA * 0.8 = 8 kW.

Why the other options are wrong

  • A. This would be if the power factor was 0.6 (10 kVA * 0.6 = 6 kW).
  • B. This would be if the power factor was 1.2, which is not possible.
  • C. 10 kW is the apparent power, not the real power, unless the power factor was 1.0.

Real Power from Apparent Power and Power Factor

Real power (kW) is the actual power consumed by a load that performs useful work, derived by multiplying the apparent power (kVA) by the power factor (PF).

  • Real power (P) is measured in watts (W) or kilowatts (kW).
  • Apparent power (S) is measured in volt-amperes (VA) or kilovolt-amperes (kVA).
  • Power factor (PF) is the ratio of real power to apparent power (PF = P/S).
  • PF indicates the efficiency of power utilization; a lower PF means higher reactive power.

Memory trick: P = S x PF, like 'P'eanut 'S'auce 'P'rovider 'F'actory.

More General Electrical Knowledge and Plan Reading questions