Master Electrician Exam (NEC)Load CalculationsMedium

A master electrician is calculating the service load for a large commercial office building. The building has 15 kW of fixed electric space heating and 12 kW of air-conditioning load. What is the demand load for these loads to be included in the service calculation, according to NEC 220.60?

  1. A8 kW
  2. B27 kW
  3. C12 kW
  4. D15 kW
Show answer & explanation

Correct answer: D. 15 kW

According to NEC 220.60, when calculating the feeder or service load for fixed electric space heating and air-conditioning, only the larger of the two connected loads is required to be used. In this case, the fixed electric space heating is 15 kW, and the air-conditioning load is 12 kW. The larger of these two is 15 kW.

Why the other options are wrong

  • A. This value is incorrect and does not represent either the heating or AC load.
  • B. This would be the sum of both loads, which is incorrect according to NEC 220.60.
  • C. This is the smaller of the two loads, which is incorrect according to NEC 220.60.

Heating & A/C Demand (NEC 220.60)

The demand load for fixed electric space heating and air-conditioning systems, where only the larger of the two connected loads is required to be included in the service or feeder calculation.

  • NEC 220.60 governs these calculations.
  • Only the larger of the heating or A/C load is counted.
  • This accounts for the fact that both systems are not typically used simultaneously at their maximum capacity.

Memory trick: Heating OR Cooling, never both full blast.