Master Electrician Exam (NEC)Load CalculationsEasy

A master electrician is performing a standard method load calculation for a single-family dwelling. The dwelling has a 12 kW electric range, a 5.5 kW electric dryer, a 3 kW water heater, and a 1.5 kW dishwasher. What is the calculated demand load for these fixed appliances before applying the general lighting and receptacle demand factor?

  1. A16.5 kW
  2. B15 kW
  3. C22 kW
  4. D12.75 kW
Show answer & explanation

Correct answer: D. 12.75 kW

According to NEC 220.53, for four or more fixed appliances, other than ranges, clothes dryers, space heating equipment, or air-conditioning equipment, a demand factor of 75% can be applied to the total nameplate rating. The range and dryer are excluded from this specific demand factor.

Why the other options are wrong

  • A. This incorrectly applies a demand factor to all appliances, including the range and dryer.
  • B. This incorrectly applies a 75% demand factor to the range and dryer, and sums the rest.
  • C. This is the sum of all appliances without any demand factor.

Fixed Appliance Demand Factor (Standard Method)

For four or more fixed appliances (excluding ranges, clothes dryers, space heating, and A/C), a 75% demand factor can be applied to their total nameplate rating in a standard load calculation.

  • Applies to four or more fixed appliances.
  • Excludes ranges, clothes dryers, space heating, and A/C.
  • Demand factor is 75% of the sum of the nameplate ratings.

Memory trick: Fixed appliances need a 'fixed' rule: sum the big ones, then demand-factor the rest.