Master Electrician Exam (NEC)Load CalculationsEasy

A three-phase, 480V motor has a full-load current (FLA) of 65A. The motor is served by a feeder. What is the minimum continuous current rating for the feeder conductors supplying this motor, according to NEC Article 430.22(A)?

  1. A81.25 A
  2. B108.33 A
  3. C97.5 A
  4. D65 A
Show answer & explanation

Correct answer: A. 81.25 A

According to NEC Article 430.22(A), conductors supplying a single motor used in a continuous duty application must have an ampacity not less than 125% of the motor's full-load current rating. Therefore, 65A * 1.25 = 81.25A.

Why the other options are wrong

  • B. Incorrect. This value does not correspond to a standard NEC multiplier for continuous motor loads.
  • C. Incorrect. This would be 150% of the FLA, which is typically for overcurrent protection, not continuous conductor sizing.
  • D. Incorrect. This is the motor's FLA, not the required conductor ampacity.

Single Motor Feeder Sizing

The calculation of the minimum ampacity required for feeder conductors supplying a single motor, based on its full-load current and duty cycle, as per NEC Article 430.22(A).

  • For continuous duty motors, conductors must be sized at 125% of the motor's FLA.
  • NEC Article 430 covers motors, motor circuits, and controllers.
  • Different multipliers apply for noncontinuous or intermittent duty motors.

Memory trick: Motor Feeder: Continuous Current needs 125% safe Amps.

More Load Calculations questions