A master electrician is calculating the feeder and service load for a multi-family dwelling with ten units. Each unit has a 12 kW electric range. The building also has a 20 kW central electric space heating system and a 15 kW central air-conditioning system. What is the demand load for the larger of the space heating or air-conditioning loads for the entire building, according to NEC 220.60?

  1. A20 kW
  2. B15 kW
  3. C35 kW
  4. D10 kW
Show answer & explanation

Correct answer: A. 20 kW

According to NEC 220.60, when calculating feeder or service loads for a dwelling unit or a feeder to a group of dwelling units, the 'larger of' the air-conditioning or space heating load is used, but not both. In this case, 20 kW (heating) is larger than 15 kW (A/C).

Why the other options are wrong

  • B. This is incorrect; 15 kW is the air-conditioning load, which is smaller than the heating load.
  • C. This is incorrect; it sums both heating and air-conditioning loads, which is prohibited by NEC 220.60.
  • D. This is incorrect; this value does not represent either the heating or air-conditioning load.

HVAC Demand (NEC 220.60)

For dwelling units or groups of dwelling units, only the larger of the air-conditioning or space heating load is included in the feeder or service load calculation, per NEC 220.60.

  • Applies to dwelling units and groups of dwelling units.
  • Only one of the two loads (A/C or heating) is selected.
  • The larger of the two loads is always chosen.
  • This rule prevents over-sizing due to non-simultaneous operation.

Memory trick: HVAC: Hot or Cold, pick the bigger story told.