Master Electrician Exam (NEC)Services, Feeders, and Branch CircuitsEasy

A master electrician is installing a new 20A, 120V branch circuit for a bathroom receptacle in a dwelling unit. The circuit will serve only this receptacle. What is the minimum size copper equipment grounding conductor (EGC) required for this circuit?

  1. A14 AWG
  2. B8 AWG
  3. C10 AWG
  4. D12 AWG
Show answer & explanation

Correct answer: D. 12 AWG

According to NEC Table 250.122, for a branch circuit protected by a 20A overcurrent device, the minimum size copper equipment grounding conductor is 12 AWG.

Why the other options are wrong

  • A. 14 AWG copper is for 15A circuits, not 20A circuits.
  • B. 8 AWG copper is significantly larger than required for a 20A circuit.
  • C. 10 AWG copper is larger than required for a 20A circuit.

Equipment Grounding Conductor Sizing (NEC 250.122)

The equipment grounding conductor (EGC) provides a low-impedance path for ground-fault current from equipment and enclosures to the service disconnecting means, ensuring overcurrent devices operate properly.

  • Sized based on the rating of the overcurrent protective device in the circuit.
  • Referenced in NEC Table 250.122.
  • Must be copper, aluminum, or copper-clad aluminum.

Memory trick: EGC: Grounding conductor, sized by the breaker's bite.