Master Electrician Exam (NEC)Services, Feeders, and Branch CircuitsMedium

A residential dwelling unit is being constructed with a 200A, 120/240V single-phase service. The service entrance conductors are 250 kcmil aluminum. What is the minimum continuous current rating required for the main service overcurrent device?

  1. A150A
  2. B225A
  3. C175A
  4. D200A
Show answer & explanation

Correct answer: D. 200A

For a 200A service, the main overcurrent device must have a continuous current rating of at least 200A. The ampacity of the service entrance conductors, 250 kcmil aluminum, is 200A (NEC 310.16, 75°C column for service conductors), which matches the required service rating.

Why the other options are wrong

  • A. 150A is too low for a 200A service.
  • B. 225A is higher than the minimum required rating, though permissible if the conductors support it.
  • C. 175A is too low for a 200A service.

Service Overcurrent Device Rating

The main service overcurrent device must have a continuous current rating not less than the noncontinuous load plus 125% of the continuous load, and not less than the ampacity of the ungrounded service-entrance conductors, or the rating of the service.

  • Must protect the service entrance conductors.
  • Must be rated for the service size (e.g., 200A service = 200A OCPD).
  • Continuous loads require 125% factor (NEC 210.20(A)).
  • Can be rounded up to the next standard size if conditions are met (NEC 240.4(B)).

Memory trick: Overcurrent Protection: Match the service, protect the wires, handle the heat.