Master Electrician Exam (NEC)Services, Feeders, and Branch CircuitsMedium

A master electrician is installing a 30A, 120/240V, single-phase branch circuit for an electric clothes dryer in a dwelling unit. The circuit conductors are 10 AWG copper with 75°C insulation. What is the minimum size required for the equipment grounding conductor (EGC) for this circuit?

  1. A10 AWG copper
  2. B12 AWG copper
  3. C8 AWG copper
  4. D14 AWG copper
Show answer & explanation

Correct answer: A. 10 AWG copper

According to NEC Table 250.122, for a branch circuit protected by a 30A overcurrent device, the minimum size copper equipment grounding conductor is 10 AWG.

Why the other options are wrong

  • B. 12 AWG copper is for 20A circuits, not 30A.
  • C. 8 AWG copper is larger than required for a 30A circuit.
  • D. 14 AWG copper is too small for a 30A circuit.

Branch Circuit Equipment Grounding Conductor Sizing

The equipment grounding conductor (EGC) for a branch circuit provides a low-impedance path for ground-fault current from the appliance or equipment to the branch-circuit overcurrent device, ensuring rapid clearing of faults.

  • Sized based on the branch-circuit overcurrent protective device rating.
  • Referenced in NEC Table 250.122.
  • Must be copper, aluminum, or copper-clad aluminum.

Memory trick: Branch EGC: The safety wire, matching the breaker's power.