A commercial building has a 400-ampere, 208Y/120-volt service. The design calls for a main service disconnect and two additional individual disconnects for specific loads, each rated at 100 amperes. All disconnects are grouped in a single enclosure. Which of the following statements is true regarding the number of service disconnects allowed by the NEC?

  1. AThe number of disconnects is unlimited as long as they are grouped together.
  2. BThree disconnects are permitted, but they must be rated equally.
  3. COnly a single main service disconnect is allowed for a service of this size.
  4. DA maximum of six service disconnects are permitted for each service.
Show answer & explanation

Correct answer: D. A maximum of six service disconnects are permitted for each service.

According to NEC 230.71(A), a maximum of six disconnects are permitted for each service entrance, grouped in a single location. The provided scenario of a main disconnect and two additional disconnects totals three, which is within the six-disconnect rule.

Why the other options are wrong

  • A. The number of disconnects is limited to six, not unlimited.
  • B. The disconnects are not required to be rated equally, only that the sum of their ratings can meet the service requirements if not individually sized for specific loads.
  • C. The NEC allows up to six disconnects, not just a single one, even for larger services, as long as they are grouped.

Six-Disconnect Rule

The NEC allows a maximum of six switches or six circuit breakers to serve as the service disconnecting means for any single service, provided they are grouped in a single location.

  • Applies to service disconnecting means.
  • Maximum of six disconnects.
  • Must be grouped in one location.
  • Found in NEC 230.71(A).

Memory trick: Six Switches Secure the Service Start.