Journeyman Electrician Exam (NEC)Control Devices and MotorsEasy

A technician is installing a new three-phase, 480V motor with a full-load current (FLA) of 65A. The motor is equipped with a separate thermal overload relay. According to NEC 430.32(A)(1), what is the maximum allowable setting for the thermal overload relay if the motor has a service factor of 1.15?

  1. A91.00A
  2. B80.60A
  3. C74.75A
  4. D84.50A
Show answer & explanation

Correct answer: C. 74.75A

For a motor with a service factor of 1.15 or greater, or a temperature rise not over 40°C, the maximum setting for a separate thermal overload relay is 125% of the motor's full-load current (FLA). Therefore, 65A * 1.15 = 74.75A.

Why the other options are wrong

  • A. This value would be incorrect, potentially using a different percentage or miscalculation.
  • B. This value would be incorrect, potentially using a different percentage or miscalculation.
  • D. This value would be incorrect, potentially using a different percentage or miscalculation.

Motor Overload Protection Setting (NEC 430.32(A)(1))

NEC 430.32(A)(1) specifies the maximum allowable setting for a separate thermal overload relay based on the motor's full-load current (FLA) and its service factor or temperature rise rating.

  • For motors with a service factor of 1.15 or greater, or a temperature rise not over 40°C, the overload device must be sized at not more than 125% of the motor's FLA.
  • For all other motors, the overload device must be sized at not more than 115% of the motor's FLA.
  • These percentages can be increased if the motor trips, up to a maximum of 140% (for 125% initial setting) or 130% (for 115% initial setting).

Memory trick: Overload Safety: Service Factor Sets the Limit!

More Control Devices and Motors questions