Journeyman Electrician Exam (NEC)Control Devices and MotorsHard

A three-phase, 480V, 50 hp motor is protected by an inverse time circuit breaker for short-circuit and ground-fault protection. The motor nameplate indicates a locked-rotor current (LRC) code of 'J'. According to NEC 430.52(C)(1) Exception No. 2, if the standard maximum rating of 250% of FLA is not sufficient to allow the motor to start, what is the absolute maximum percentage of the motor's full-load current (FLA) that the circuit breaker rating is permitted to be increased to?

  1. A300%
  2. B400%
  3. C600%
  4. D800%
Show answer & explanation

Correct answer: B. 400%

According to NEC 430.52(C)(1) Exception No. 2, if an inverse time circuit breaker sized at 250% of the motor's FLA (as per Table 430.52) is not sufficient to allow the motor to start, its rating can be increased, but it shall not exceed 400% of the motor's full-load current. The locked-rotor code 'J' indicates a relatively high LRC, which might necessitate this increase.

Why the other options are wrong

  • A. 300% is the maximum for non-time-delay fuses, not inverse time circuit breakers in this exception.
  • C. 600% is incorrect for inverse time circuit breakers under these conditions.
  • D. 800% is the maximum for instantaneous trip circuit breakers, not inverse time circuit breakers.

Motor Short-Circuit Protection Adjustment (NEC 430.52 Exceptions)

NEC 430.52(C)(1) includes exceptions that allow increasing the rating of branch-circuit short-circuit and ground-fault protective devices beyond the standard table values if the motor cannot start, with specific upper limits depending on the device type.

  • The standard maximum for inverse time circuit breakers is 250% of FLA (Table 430.52).
  • If 250% is insufficient for starting, it can be increased, but not to exceed 400% of FLA.
  • Similar exceptions exist for other protective device types (e.g., non-time-delay fuses up to 400%).

Memory trick: If 250% isn't enough, an inverse breaker can go up to 400% for that motor's tough start.