Journeyman Electrician Exam (NEC)Wiring Methods and MaterialsHard

A commercial electrician is installing a new circuit in a Class I, Division 1 hazardous location. Which of the following wiring methods is NOT permitted for use in this type of hazardous location?

  1. AType MC cable with a gas/vapor-tight continuous corrugated metallic sheath
  2. BExplosionproof flexible metal conduit
  3. CThreaded rigid metal conduit (RMC)
  4. DLiquidtight flexible metal conduit (LFMC)
Show answer & explanation

Correct answer: D. Liquidtight flexible metal conduit (LFMC)

NEC 501.10(A) specifies the wiring methods permitted in Class I, Division 1 locations. Rigid metal conduit (RMC), intermediate metal conduit (IMC), and specific types of Type MC cable (with a gas/vapor-tight continuous corrugated metallic sheath, an overall jacket, and identified for the purpose) are permitted. Liquidtight flexible metal conduit (LFMC) is generally not permitted in Class I, Division 1 locations, except for specific short sections for flexibility where approved fittings are used, but it's not a primary wiring method for the full installation.

Why the other options are wrong

  • A. Permitted. Specific types of MC cable are allowed, identified for the purpose, with a continuous corrugated metallic sheath and overall jacket (NEC 501.10(A)(1)(c)).
  • B. Permitted. Explosionproof flexible metal conduit (typically using fittings listed for the purpose) is allowed for short flexible connections (NEC 501.10(A)(2)).
  • C. Permitted. Threaded RMC is a common and approved wiring method for Class I, Division 1 locations (NEC 501.10(A)(1)).

Class I, Division 1 Wiring

Wiring methods in Class I, Division 1 hazardous locations must be explosionproof and designed to prevent the ignition of flammable gases or vapors.

  • NEC 501.10(A) lists permitted wiring methods.
  • Rigid metal conduit (RMC) and Intermediate metal conduit (IMC) with threaded connections are primary methods.
  • Specific types of Type MC cable are also permitted.
  • Flexible connections generally require explosionproof flexible fittings or listed flexible conduit.

Memory trick: RMC, IMC, MC are tough, LFMC is not enough!