A 20 hp, 230V, three-phase Squirrel Cage Induction Motor with a service factor of 1.0 is being installed. The motor branch-circuit conductors are sized for 125% of the motor's full-load current (FLA). According to NEC Table 430.250, the motor's FLA is 54A. What is the minimum ampacity required for the branch-circuit conductors?

  1. A67.5 A
  2. B70 A
  3. C54 A
  4. D81 A
Show answer & explanation

Correct answer: A. 67.5 A

According to NEC 430.22(A), branch-circuit conductors supplying a single motor used in a continuous duty application must have an ampacity not less than 125% of the motor's full-load current (FLA). Therefore, 54A * 1.25 = 67.5A.

Why the other options are wrong

  • B. This is a standard conductor ampacity, but not the calculated minimum based on 125% of FLA.
  • C. This is the motor's FLA, not the required conductor ampacity.
  • D. This is 150% of the motor's FLA, which is higher than the minimum required.

Motor Branch-Circuit Conductor Sizing

NEC 430.22(A) requires that motor branch-circuit conductors for continuous duty motors have an ampacity not less than 125% of the motor's full-load current (FLA) to ensure they can safely carry the motor's running current and accommodate minor overloads.

  • Conductor ampacity is calculated as 125% of the motor's FLA for continuous duty motors.
  • This sizing accounts for normal operating conditions and minor, sustained overloads.
  • The FLA is typically obtained from the motor nameplate or NEC Tables 430.247 through 430.250.

Memory trick: For Continuous Duty, Conductors need a Quarter More power.