Journeyman Electrician Exam (NEC)Control Devices and MotorsMedium

A variable frequency drive (VFD) is used to control a 25 hp, 480V, three-phase motor. The VFD's output conductors to the motor are being sized. The motor has a nameplate FLA of 34A. According to NEC Article 430.122(A), what minimum ampacity is required for the conductors between the VFD and the motor?

  1. A47.6A
  2. B38A
  3. C34A
  4. D42.5A
Show answer & explanation

Correct answer: D. 42.5A

NEC 430.122(A) states that conductors connecting the output of a variable frequency drive to a motor shall have an ampacity not less than 125% of the motor's full-load current rating as determined by 430.6(A)(1) or 430.6(A)(2). In this case, the motor FLA is 34A. Therefore, 34A * 1.25 = 42.5A.

Why the other options are wrong

  • A. This value (140% of FLA) is higher than the minimum required by NEC 430.122(A).
  • B. This value is less than the required 125% of FLA.
  • C. This is the motor's FLA, which is not sufficient for VFD output conductors.

VFD Output Conductor Sizing (NEC 430.122(A))

Conductors connecting the output of a variable frequency drive (VFD) to a motor must have an ampacity not less than 125% of the motor's full-load current rating.

  • Applies to conductors between VFD and motor.
  • Minimum ampacity is 125% of motor FLA.
  • Different from VFD input conductor sizing.
  • Accounts for potential harmonic distortion and motor heating.

Memory trick: VFD's output needs a 'quarter-extra' current capacity.