CSLB C-10 Electrical ContractorEquipment and InstallationHard

An electrician is installing two 3-phase, 480-volt feeders in the same conduit. Each feeder consists of three 4 AWG THHN copper conductors. What is the maximum number of current-carrying conductors for the purpose of adjusting ampacity according to NEC Table 310.15(C)(1)?

  1. A4
  2. B6
  3. C3
  4. D7
Show answer & explanation

Correct answer: B. 6

Each 3-phase feeder has three current-carrying conductors (L1, L2, L3). Since there are two such feeders in the same conduit, the total number of current-carrying conductors is 3 + 3 = 6. The neutral conductor in a 3-phase, 4-wire system with balanced loads is not counted as a current-carrying conductor for ampacity adjustment, but the question specifies 3-phase feeders, implying 3 current-carrying conductors per feeder.

Why the other options are wrong

  • A. This is incorrect; it might apply to some single-phase multiwire circuits but not two 3-phase feeders.
  • C. This would be correct for a single 3-phase feeder.
  • D. This would be for two 3-phase feeders plus a neutral or ground, but the question specifies 'current-carrying conductors' for ampacity adjustment.

Ampacity Adjustment for Multiple Conductors

When more than three current-carrying conductors are installed in a raceway or cable, the ampacity of each conductor must be reduced by an adjustment factor from NEC Table 310.15(C)(1).

  • Only current-carrying conductors are counted.
  • Neutral conductors in a balanced 3-phase, 4-wire system are generally not counted.
  • Equipment grounding conductors are never counted.

Memory trick: Count Conductors: 'L'ive 'P'hases 'O'nly (unless neutral is unbalanced).

More Equipment and Installation questions