CSLB C-10 Electrical ContractorEquipment and InstallationEasy

A client requests a new dedicated 20-ampere, 120-volt branch circuit for a single-phase, continuous-duty motor. The motor has a nameplate full-load current (FLC) of 15 amperes. What is the minimum size copper THWN-2 conductor required for this branch circuit?

  1. A8 AWG
  2. B12 AWG
  3. C14 AWG
  4. D10 AWG
Show answer & explanation

Correct answer: B. 12 AWG

Motor branch-circuit conductors must be sized at not less than 125% of the motor’s FLC. For a 15-ampere motor, 125% is 18.75 amperes. A 12 AWG THWN-2 conductor is rated for 20 amperes at 75°C, which is sufficient.

Why the other options are wrong

  • A. 8 AWG is significantly oversized and not the minimum required for this application.
  • C. 14 AWG is rated for 15 amperes, which is less than 125% of the motor's FLC.
  • D. 10 AWG is oversized and not the minimum required for this application.

Motor Branch-Circuit Conductor Sizing

Conductors supplying a single motor used in continuous duty must have an ampacity of at least 125% of the motor's full-load current.

  • Applies to continuous-duty motors.
  • Minimum ampacity = FLC x 1.25.
  • Conductor ampacity must be chosen from appropriate temperature column (e.g., 75°C for THWN-2).

Memory trick: Motor Conductors Need Extra Juice: Multiply FLC by 1.25.