Journeyman Electrician Exam (NEC)Control Devices and MotorsHard

A motor control circuit utilizes a Class 2 power-limited transformer for its control power. The primary side of the transformer is connected to a 480V circuit, and the secondary side provides 24V AC. According to NEC 430.72(A), which statement accurately describes the overcurrent protection requirements for the primary side of this control transformer?

  1. AThe primary side does not require separate overcurrent protection if the branch-circuit overcurrent device is rated 20A or less.
  2. BThe primary side must be protected at not more than 125% of the transformer's rated primary current.
  3. CThe primary side must be protected at not more than 200% of the transformer's rated primary current.
  4. DThe primary side overcurrent device must not be rated over 20A for a 480V primary.
Show answer & explanation

Correct answer: A. The primary side does not require separate overcurrent protection if the branch-circuit overcurrent device is rated 20A or less.

NEC 430.72(A) Exception No. 2 specifies that if the control circuit transformer is a Class 2 power-limited transformer, primary overcurrent protection is not required where the control circuit conductors are protected by the branch-circuit overcurrent protective device. This exception typically applies when the branch-circuit overcurrent device is rated 20A or less, as defined in other articles (e.g., 725.121(A)(1) for Class 2 circuits). The question implies this condition by stating 'Class 2 power-limited transformer'. If the branch circuit OCPD protects the primary, no separate primary protection is needed.

Why the other options are wrong

  • B. This is a general rule for transformers, but specific exceptions apply for Class 2 transformers in motor control (430.72(A) Exception No. 2).
  • C. 200% is not the correct maximum for primary protection of control transformers; typically it's 125% or specific values based on transformer rating (NEC 430.72(C)).
  • D. This is incorrect. The 20A limit is usually for the branch circuit OCPD that *protects* the primary, not a separate primary OCPD rating for a 480V primary.

Control Transformer Overcurrent Protection (NEC 430.72(A))

NEC 430.72(A) outlines the requirements for overcurrent protection of control circuit transformers, including specific exceptions for Class 2 power-limited transformers where protection can be provided by the branch-circuit overcurrent device.

  • Primary protection is generally required at not more than 125% of the rated primary current.
  • Exception No. 2 allows omission of primary protection for Class 2 power-limited transformers if the branch-circuit OCPD provides adequate protection.
  • Secondary protection is also required, typically based on conductor ampacity.

Memory trick: Primary protection: 125% or branch circuit for Class 2, don't let it burn out!