Journeyman Electrician Exam (NEC)Equipment and DevicesMedium

A journeyman electrician is installing a 277-volt LED luminaire in a commercial warehouse. What is the maximum continuous load permitted on a 20-ampere branch circuit supplying this luminaire?

  1. A24 amperes
  2. B25 amperes
  3. C16 amperes
  4. D20 amperes
Show answer & explanation

Correct answer: C. 16 amperes

For continuous loads, the maximum overcurrent device rating must not exceed 125% of the continuous load. Conversely, the continuous load must not exceed 80% of the branch-circuit rating. For a 20-ampere circuit, 20 A * 0.80 = 16 amperes.

Why the other options are wrong

  • A. This exceeds the 80% continuous load limit for a 20-ampere circuit.
  • B. This exceeds the 80% continuous load limit for a 20-ampere circuit.
  • D. This represents the full rating of the branch circuit, which is only allowed for non-continuous loads or if the overcurrent device is rated for 100% continuous operation.

Continuous Load Limit for Branch Circuits

For continuous loads (expected to operate for 3 hours or more), the maximum load current must not exceed 80% of the branch circuit's overcurrent device rating, unless the overcurrent device assembly is listed for 100% continuous operation.

  • Continuous load is 3 hours or more.
  • Load must not exceed 80% of OCPD rating.
  • This rule applies to the branch circuit conductors and overcurrent device.

Memory trick: Long loads need a smaller share of the circuit's power.