Master Electrician Exam (NEC)Grounding and BondingHard

A master electrician is installing a new 480V, 3-phase, 4-wire wye system for a commercial kitchen. The main service will be located in a dedicated electrical room. What is the minimum size copper main bonding jumper required if the ungrounded service-entrance conductors are 700 kcmil copper?

  1. ANo. 2/0 AWG
  2. BNo. 1/0 AWG
  3. CNo. 3/0 AWG
  4. DNo. 4/0 AWG
Show answer & explanation

Correct answer: A. No. 2/0 AWG

According to NEC 250.28(D)(1) and Table 250.102(C)(1), the main bonding jumper shall not be smaller than the sizes shown in Table 250.102(C)(1). For ungrounded service-entrance conductors of 700 kcmil copper, the minimum size copper main bonding jumper required is No. 2/0 AWG.

Why the other options are wrong

  • B. No. 1/0 AWG is for service conductors up to 400 kcmil copper.
  • C. No. 3/0 AWG is for service conductors up to 800 kcmil copper.
  • D. No. 4/0 AWG is for service conductors up to 1100 kcmil copper.

Main Bonding Jumper Sizing

The main bonding jumper size is determined by the size of the largest ungrounded service-entrance conductor or equivalent area for parallel conductors, referenced in NEC Table 250.102(C)(1).

  • Sized based on the largest ungrounded service conductor.
  • Found in NEC 250.28(D) and Table 250.102(C)(1).
  • Ensures a low-impedance path for fault current at the service.

Memory trick: Bonding jumper size: service conductors tell the tale.

More Grounding and Bonding questions