Master Electrician Exam (NEC)Grounding and BondingMedium

A master electrician is installing a new 480V, 3-phase, 3-wire delta service for an industrial facility. The service entrance conductors are 300 kcmil copper. What is the minimum size copper grounding electrode conductor (GEC) required for this service?

  1. ANo. 2/0 AWG
  2. BNo. 2 AWG
  3. CNo. 4 AWG
  4. DNo. 1/0 AWG
Show answer & explanation

Correct answer: B. No. 2 AWG

According to NEC 250.66 and Table 250.66, the GEC is sized based on the largest ungrounded service-entrance conductor. For 300 kcmil copper service conductors, the minimum size copper GEC required is No. 2 AWG.

Why the other options are wrong

  • A. This size is significantly larger than required.
  • C. This size is too small for 300 kcmil service conductors.
  • D. This size is larger than required.

GEC Sizing for Services

The grounding electrode conductor (GEC) for a service is sized based on the largest ungrounded service-entrance conductor, referencing NEC Table 250.66.

  • Sized by largest ungrounded service conductor.
  • Table 250.66 is the reference.
  • Connects GES to service equipment.

Memory trick: GEC size, the service it ties.