CSLB C-10 Electrical ContractorEquipment and InstallationMedium

An electrician installs a 125-volt, 15-ampere receptacle on a countertop 4 feet from the edge of a sink in an employee break room within a commercial office building. Per NEC 210.8(B), is GFCI protection required for this receptacle?

  1. ANo, GFCI protection in commercial break rooms only applies to receptacles serving dishwashers.
  2. BYes, but only if the receptacle serves a 20-ampere small appliance branch circuit.
  3. CYes, GFCI protection is required because the receptacle is within 6 feet of the sink's edge.
  4. DNo, GFCI protection is only required for receptacles in dwelling unit kitchens, not commercial break rooms.
Show answer & explanation

Correct answer: C. Yes, GFCI protection is required because the receptacle is within 6 feet of the sink's edge.

NEC 210.8(B) requires GFCI protection for 125-volt, 15- and 20-ampere receptacles installed within 6 feet of the outside edge of a sink in other than dwelling units, which includes break room sinks in commercial buildings.

Why the other options are wrong

  • A. GFCI requirements are based on proximity to the sink, not the appliance served.
  • B. The ampere rating of the branch circuit does not exempt the receptacle from GFCI protection.
  • D. 210.8(B) explicitly extends GFCI requirements to non-dwelling occupancies.

GFCI Near Sinks — Non-Dwelling (210.8(B))

In other than dwelling units, 125V, 15/20A receptacles within 6 feet of a sink's outside edge require GFCI protection.

  • Applies to break rooms, commercial kitchens, and similar spaces
  • Measured from the outside edge of the sink bowl
  • Mirrors the dwelling unit rule but covers commercial/industrial settings

Memory trick: 'Six feet from any sink, plug in a GFCI link.'