CSLB C-20 HVAC ContractorPlanning and LayoutHard

A Manual S equipment selection process for a home in a high-desert California climate zone uses a 1% cooling design temperature of 105°F. The condensing unit's nameplate capacity is rated at standard AHRI test conditions of 95°F outdoor temperature. What must the contractor do to correctly verify equipment capacity at design conditions?

  1. AIncrease equipment sensible capacity but ignore latent capacity changes at higher temperatures
  2. BUse the AHRI-rated capacity directly since nameplate ratings apply at all outdoor temperatures
  3. CAssume capacity increases at higher outdoor temperatures due to greater ΔT across the coil
  4. DApply the manufacturer's extended performance data table to find actual capacity at 105°F
Show answer & explanation

Correct answer: D. Apply the manufacturer's extended performance data table to find actual capacity at 105°F

AHRI nameplate ratings are only valid at the standard 95°F test condition. Manual S requires contractors to consult manufacturer extended performance data (capacity tables at various outdoor temperatures) to determine true sensible and latent capacity at the actual 1% design condition, since capacity typically decreases as outdoor temperature rises above 95°F.

Why the other options are wrong

  • A. Both sensible and latent capacity are affected and must be checked together.
  • B. Nameplate ratings are condition-specific and cannot be applied universally.
  • C. Capacity actually decreases, not increases, as outdoor temperature rises above rating conditions.

Manual S Extended Performance Data

Manual S requires verifying equipment capacity using manufacturer extended performance tables when the site's design temperature differs from the standard AHRI 95°F rating condition.

  • AHRI nameplate ratings are only valid at 95°F outdoor condition
  • Capacity generally decreases as outdoor temperature rises above 95°F
  • Extended performance tables list capacity across a range of temperatures/CFM

Memory trick: Don't trust the nameplate past its test conditions—check the extended chart.