CSLB C-20 HVAC ContractorPlanning and LayoutEasy

A residential split-system air conditioner is rated at 3 tons of cooling capacity. Using the standard rule-of-thumb airflow requirement commonly applied for typical comfort cooling systems, what design supply airflow should the duct system be sized to deliver?

  1. A1,500 CFM
  2. B900 CFM
  3. C1,200 CFM
  4. D1,050 CFM
Show answer & explanation

Correct answer: C. 1,200 CFM

The standard rule-of-thumb airflow for residential comfort cooling is approximately 400 CFM per ton of cooling capacity. For a 3-ton system: 3 tons × 400 CFM/ton = 1,200 CFM.

Why the other options are wrong

  • A. Corresponds to 500 CFM/ton, more typical of high-latitude dry climates, not standard design.
  • B. Corresponds to only 300 CFM/ton, too low for standard comfort cooling.
  • D. Not a standard rule-of-thumb multiple for tonnage.

CFM per Ton Rule of Thumb

A quick estimating guideline stating that residential cooling systems typically require about 400 CFM of airflow per ton of cooling capacity.

  • 1 ton = 12,000 Btu/hr
  • 400 CFM/ton is standard for comfort cooling
  • Actual design should still be verified with Manual D

Memory trick: Four hundred per ton keeps the airflow right where it belongs.